Modbus Register Address Ranges of the Measurement Data
All the Modbus registers comprise an address range of 0...65536, with every Modbus register occupying 2 bytes of the
data logger.
The following Modbus register address ranges are available for measurement data:
Tab. 5.1: Modbus register address ranges
measurement data
measuring
channel
Modbus register address range
single physical quantity
Every physical quantity with all corresponding parameters is
provided in a block of 16 Modbus registers (see chapter 6).
A
1000...1415
B
2000...2415
Y
10000...10415
Z
9000...9415
single diagnostic value
Every diagnostic value with all correspon-
ding parameters is provided in a block of
16 Modbus registers.
channel-dependent
diagnostic value
(see chapter 6)
A
1700...1795
B
2700...2795
Y
10700...10795
Z
9700...9795
channel-
independent
diagnostic value
(see section 8.1)
-
30000...30159
several measured values
The measured values are provided as scaled floating point
numbers (see chapter 7).
A
15000...15051
B
16000...16051
Y
20000...20051
Z
19000...19051
several state values of the physical quantities
The state values of the physical quantities are provided as inte-
gers (see chapter 7).
A
15200...15225
B
16200...16225
Y
20200...20225
Z
19200...19225
several diagnostic values
The diagnostic values are provided as scaled floating point
numbers (see chapter 7).
A
15300...15311
B
16300...16311
Y
20300...20311
Z
19300...19311
several state values of the diagnostic values
The state values of the diagnostic values are provided as inte-
gers (see chapter 7).
A
15400...15405
B
16400...16405
Y
20400...20405
Z
19400...19405
Содержание FLUXUS ADM 5 07 Series
Страница 4: ...Modbus Server Supplement to User Manual 4 SU_ModbusV2 8 2015 03 02...
Страница 6: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 6 SU_ModbusV2 8 2015 03 02...
Страница 46: ...Modbus Server Erg nzung zur Bedienungsanleitung DEUTSCH 46 SU_ModbusV2 8 2015 03 02...
Страница 48: ...Modbus Server Supplement to User Manual ENGLISH 48 SU_ModbusV2 8 2015 03 02...