VESDA-E VEU-A10 Product Guide
www.xtralis.com
39
4.3.6
Relays
The relays, located on the main processor card, interface to the Fire Alarm Control Panel (FACP) to
communicate faults, alarms and disabled states. The relays can be programmed using Xtralis VSC. Relays 3
and 6 are permanently set for Urgent Fault and Fire 1 respectively. Table 4-22 below illustrates the default
assignments of functions (conditions) to relays and summarizes the default behavior of each relay. Section
5.5.10 describes how to configure the relay behavior using Xtralis VSC. It is possible to assign more than one
condition to a relay.
Fire 1 Relay
If a detector relay is to be used to signal fire alarm to the Fire Alarm Control Panel (FACP) then the Fire 1 relay
must be used.
Fault and Fire 1 Relay Terminals
The Urgent and Minor Fault relays are energized during normal operation while the Fire 1 relay is only
energized when a Fire 1 is detected. The operation of the relays are summarized in the following table.
Table 4-1: Typical Relay Operation
URGENT FAULT Relay
All Other Relays
No Fault
(Energized)
Fault
or unpowered state
No Fire
(De-energized)
Fire
Relay Assignments and Behaviour
l
Relays 1, 2, 4, 5 and 7 are fully configurable. For example, Relay 5 could be configured to de-energize on
Alert
l
Relays 3 and 6 are fixed to Urgent Fault and Fire 1 respectively. These relays may be assigned additional
conditions.
Relay #
Default
Assignment
Default to
Normally
Energized
Description for default configuration
Configurability
1
Disable
(Isolate) and
Standby
No
Energizes when an operator disables
(isolates) the detector. Also energizes when
the operator puts the detector into Standby
mode.
Fully
configurable
2
Minor Fault
Yes
De-energizes when a Minor Fault is
detected.
Fully
configurable
3
Urgent Fault,
Disable,
Standy
Yes
De-energizes when an Urgent Fault is
detected or when Disable or Standby
occurs.
Note that Relay 3 is fixed Normally
Energized in order to ensure that a fault will
be signaled when power to the VEU-A10 is
removed. See Table 4-1.
Urgent Fault
cannot be
removed. Other
conditions can
be added.
Fixed Normally
Energized
4
Alert
No
Energizes when the Alert alarm is initiated.
Fully
configurable
Table 4-2: Default Relay Assignments
Содержание VESDA-E VEU-A10
Страница 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Страница 2: ......
Страница 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEU A10 Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Страница 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Страница 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...