VESDA-E VEU-A10 Product Guide
58
www.xtralis.com
5.4
Commands
The following commands are able to be issued to the detector. As indicated below in Table 5-2, a small
number of basic commands can be executed from the detector via buttons, while the full range of commands
can be executed using the Xtralis VSC software.
Command
Description
Execute From
A button
on the
Detector
Xtralis VSC
Software
Disable (Isolate)
The Disable command disables all the output relays
associated with the detector. The aspirator remains
active.
Enable
The Enable command enables all of the output
relays associated with the detector.
Go to Standby
The Go to Standby sets the detector to Standby
mode. See Section 7.1 on page 79 for a description
of Standby mode.
End Standby
The End Standby command is available when the
detector is in Standby mode. The End Standby
command causes the detector to exit Standby
mode.
Reset
The Reset command unlatches all latched alarms
and faults, and returns relays to their normal state.
Clears the Xtralis VSC active event list.
Reset does not enable a disabled detector or
reactivate a detector that is in Standby mode.
Start Normalize Air Flow Starts the air flow normalization process for the
selected detector.
The normalization process determines the reference
flow rate.
The detector can be in normal or disabled mode, but
not standby mode.
The aspirator remains on throughout the
normalization process and no fault is reported unless
the process fails to successfully complete.
The normalizing status may be observed on the
"detailed status" tab in the Xtralis VSC software.
To normalize the detector using the internal
AutoConfig button, press and hold the button until
the AutoConfig LED illuminates, then release the
button. To cancel the normalization process, press
and hold the button for 5 seconds. The LED will turn
off.
Table 5-2: Detector Commands
Содержание VESDA-E VEU-A10
Страница 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Страница 2: ......
Страница 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEU A10 Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Страница 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Страница 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...