VESDA-E VEU-A10 Product Guide
60
www.xtralis.com
Command
Description
Execute From
A button
on the
Detector
Xtralis VSC
Software
Start Minor Fault Test
Generates a minor fault on the detector and de-
energizes the fault relay for 2 minutes.
Start Alarm Test
Simulates full scale smoke level which causes the
Alert, Action , Fire 1 and Fire 2 alarm conditions to
occur.
Alarm relays will energize unless the detector is
disabled.
Start Air Flow Fault Test Tests the air flow sensing system by shutting down
the aspirator.
Start Relay Test
Tests the available relays by activating and
deactivating as required.
Start LED Test
Tests each LED by cycling through all LEDs on the
detector display panel.
Return to Factory
Defaults
Restores the configuration of the detector to the
initial factory default values.
Set System Date and
Time
Sets the detector date and time.
Table 5-2: Detector Commands (continued...)
Содержание VESDA-E VEU-A10
Страница 1: ...VESDA E VEU A10 Product Guide November 2018 Document 22077_12 Part Number 30334 ...
Страница 2: ......
Страница 10: ...VESDA E VEU A10 Product Guide 4 www xtralis com This page is intentionally left blank ...
Страница 22: ...VESDA E VEU A10 Product Guide 16 www xtralis com This page is intentionally left blank ...
Страница 54: ...VESDA E VEU A10 Product Guide 48 www xtralis com This page is intentionally left blank ...
Страница 82: ...VESDA E VEU A10 Product Guide 76 www xtralis com This page is intentionally left blank ...
Страница 100: ...VESDA E VEU A10 Product Guide 94 www xtralis com 1 2 3 Figure 7 21 Undo Sampling Module screws ...
Страница 106: ...VESDA E VEU A10 Product Guide 100 www xtralis com This page is intentionally left blank ...
Страница 110: ...VESDA E VEU A10 Product Guide 104 www xtralis com This page is intentionally left blank ...
Страница 116: ...VESDA E VEU A10 Product Guide 110 www xtralis com Z zone 59 61 79 105 ...