www.flamcogroup.com
© 2014 Flamco group. All rights reserved.
We reserve the right to change designs and technical specifications of our products
.
Rev 8.1 Aug-15 Page
18
/
44
#
Menu Item
Function
Default
Value
8
PUMP 2 COUNT
The cumulative number of pump starts for pump 2.
This is a cumulative counter, the value of which cannot be modified. If using the
engineer’s code, the counter can be reset to zero by holding the (MUTE)
button.
-
9
PUMP 2 HOURS
The cumulative run time in hours for pump 2.
This is a cumulative timer, the value of which cannot be modified. If using the
engineer’s code, the counter can be reset to zero by holding the (MUTE)
button.
-
10
ALARM COUNT
The cumulative number of all alarm incidents.
This is a cumulative counter, the value of which cannot be modified. If using the
engineer’s code, the counter can be reset to zero by holding the (MUTE)
button.
-
11
POWER
INTERRUPTED
The cumulative number of power interruptions (i.e. controller turned off/
power cut).
This is a cumulative counter, the value of which cannot be modified. If using the
engineer’s code, the counter can be reset to zero by holding the (MUTE)
button.
-
12
PULSE
When enabled, if a pump has been inactive for 60 days, it will start and run for
2 seconds.
This is to prevent the pumps from seizing.
YES
13
EXCESSIVE
START
When enabled, if there are more than 3 individual pump runs within an 8 hour
period, the unit will register an <EXCESSIVE DEMAND> alarm.
Enabling this option may cause false alarms on some systems.
NO
14
SERVICE
When enabled, a service reminder will be displayed after 12 months from when
the option was enabled.
To reset the service reminder, set the value to ‘NO’ and exit the menu. Then,
re-enter the menu and set the value to ‘YES’ again.
NO
15
FILL SYSTEM
When enabled, the <LOW PRESSURE> and <FLOOD LIMIT> alarms will be
disabled, and pump 1 will run continuously for up to 24 hours until the cold fill
pressure has been reached.
Once the cold fill pressure has been reached, this option will automatically be
deactivated, and the low pressure alarm and flood limit will be reactivated.
This function is used to fill a system that is empty or at low pressure.
Care must be taken using this option as the flood limit alarm is disabled,
increasing the risk of flooding.
This option cannot be enabled on Mini pressurisation units.
NO
If using the customer code, the menu will end at this point. After pressing (SET) once more, the
controller will display “SAVING...” and return to normal operating mode. If using the engineer’s
code, additional menu items will be displayed.
The following settings are all pre-programmed in the factory and should not need to be
modified on site. If these settings appear to have been reset, the most likely cause is a power
spike. If this problem persists, a power filter may be required.