manualshive.com logo in svg
background image

 

© 2017 United Technologies Corporation 

1 / 2 

P/N 3102073-

EN • REV 005 • ISS 22SEP17 

 

GSA-T3T4 Temporal Pattern 
Generator Installation Sheet 

Description 

The model GSA-T3T4 Temporal Pattern Generator is an addressable 
device that generates sound patterns for fire or carbon monoxide (CO) 
alarms for compatible audible (sounder) bases. Table 1 and Figure 1 
below show the pattern characteristics. 

Table 1: Temporal patterns 

Name  Code 

For 

Description of pattern per cycle 

TC3 

NFPA 72 

Fire 

0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 
0.5 s on, 1.5 s off 

TC4 

NFPA 720  CO  

0.1 s on, 0.1 s off, 0.1 s on, 0.1 s off, 
0.1 s on, 0.1 s off, 0.1 s on, 5.1 s off 

 

Figure 1: Temporal pattern wavelengths 

 

The GSA-T3T4 module uses two addresses on the signaling line 
circuit (SLC). Address 1 is tied to Channel 1; Address 2 is tied to 
Channel 2. Channel 1 always has the highest priority. 

Channel selection 

The control panel sends synchronization and channel commands to 
the GSA-T3T4. Channel selection determines the pattern. The control 
panel can also send silencing commands to the GSA-T3T4. 

During system initialization, the SLC controller determines which 
pattern plays on each channel, depending on the marketplace setting. 
For example, in the US and Canadian marketplaces, a fire alarm takes 
priority over a CO alarm, so the TC3 pattern is assigned to Channel 1. 
Settings for other markets are governed by local requirements. 

Synchronization 

When an alarm condition occurs, the detector notifies the panel and 
the panel commands the GSA-T3T4 to activate the T3T4 riser. The 
GSA-T3T4 generates the appropriate pattern and synchronizes all the 
audible bases on a single SLC. The SLC controller synchronizes 
multiple GSA-T3T4s installed on the same SLC. 

Silencing the GSA-T3T4 

The alarm signal continues until the system resets or is manually 
silenced. The GSA-T3T4 can receive silencing commands from the 
control panel. 

LEDs 

Diagnostic LEDs provide visible indication of the status of the module 
through the cover plate: 

• 

Normal: green LED flashes 

• 

Alarm/active: red LED flashes 

Personality code 

The default personality code is 70, Unsupervised Relay Output. This 
configures the GSA-T3T4 to select the desired sound pattern based on 
the activated channel. 

Installation 

Install this device in accordance with the latest editions of 
CAN/CSA-6.19, CAN/ULC-S524, CSA C22.1, NFPA 72, NPFA 720, 
and the local authority having jurisdiction. 

Caution: 

Electrical supervision requires the wire run to be broken at 

each terminal. Do not loop the signaling circuit field wires around the 
terminals. 

Notes 

• 

The GSA-T3T4 Temporal Pattern Generator is shipped from the 
factory as an assembled unit; it contains no user-serviceable parts 
and should not

 

be disassembled. 

• 

Only one module is required for each T3T4 riser. 

• 

When determining allowable wire resistance, refer to the voltage 
rating of the module, the signaling appliance, and the control panel 
specifications. 

• 

Wire in accordance with NFPA 70 

National Electrical Code 

or 

CSA C22.1 

Canadian Electrical Code

• 

Each terminal on the GSA-T3T4 module is limited to a single 
conductor. 

• 

Strip 1/4 in. (about 6 mm) from the ends of all wires that connect to 
the terminal block of the module. Exposing more bare wire may 
cause a ground fault and exposing less wire may result in a faulty 
connection. 

To install the module: 

1.  Verify that all field wiring is free of opens, shorts, and ground 

faults. 

2.  Make the wiring connections as shown in Figure 3. 

3.  Install the module as shown in Figure 2. See 

“Specifications” on 

page 2 for compatible electrical boxes. 

Figure 2: Mounting in a single-gang box 

 

(1)  Compatible electrical box 
(2)  GSA-T3T4 
(3)  Wall plate 

(4)  #6-32 × 1/2 screws 
(5)  #4-24 × 1/2 screw 

TC4 (5.8 s) 

TC3 (4.0 s) 

(1)

(2)

(3)

(4)

(5)

(4)

Отзывы: