Fläkt Woods
3099 US 03.02
22
Specifications are subject to alteration without notice
PUMA (A–F) Rotary heat exchanger
TECHNICAL HANDBOOK
Installation
Rotary heat exchangers can be supplied for installation in
air handling units, in the ducting or in a plant room. All
variants and sizes can be installed either horizontally or
vertically.
Fig. 23
For dimension A, see page 24.
Fig. 24
The heat exchanger should rest on a flat supporting sur-
face. If other components, such as a duct or unit section,
are connected to the top of the heat exchanger, they
must not rest on the exchanger.
A supporting center beam must be provided for size
200 and larger units. The maximum permissible deflec-
tion of the load-bearing centre beam when supporting
the weight of the heat exchanger and any other compo-
nents is 0.04 inches.
M
M
Frånluft
Tilluft
1. Horisontellt montage
Fig. 22
Drivmotor
Placering av varvtalsregulator
vid mindre växlare
Eventuellt
radiostörningsskydd
Eventuell placering av varvtals-
regulator vid större växlare
Drivmotor
=
A 100
=
Exhaust air
Supply air
Drive motor
1. Horizontal installation
Fig. 21
Location of the speed controller
on smaller heat exchangers
Radio interference suppressor,
if any
Location of the speed controller
on larger heat exchangers
Drive motor
Installing the speed controller
M
M
M
M
2. Vertikalt montage –
horisontell delning
3.Vertikalt montage –
vertikal delning
Fig. 23
Fig. 22
2. Vertical installation -
horizontally split
3. Vertical installation -
vertically split