background image

FläktGroup 

DC_9503GB 20180817_R0

Specifications are subject to alteration without notice.

Fire Damper ETCE and ETCS - Instructions for Installation, Operation and Maintenance

5

Size ØD (mm)

Installation opening Ø (mm)

100

125

150

160

200

250

300

315

400

500

630

800

1000

175 – 195

175 – 195

200 – 220

210 – 230

250 – 270

300 – 320

350 – 370

365 – 385

450 – 470

550 – 570

680 – 700

850 – 870

1050 – 1070

Size ØD (mm)

Installation opening Ø (mm)

100

125

150

160

200

250

300

315

400

500

630

800

1000

135 – 137

135 – 137

160 – 162

170 – 172

210 – 212

260 – 262

310 – 312

325 – 327

410 – 412

510 – 512

640 – 642

810 – 812

1010 – 1012

Installation of fire damper into rigid  

building elements (walls and 

intermediate floors) with fire  

classification EI 60 (Fig. 1 and Fig. 4)

1.  Installation opening in the rigid wall or intermediate floor 

must comply with the dimensions given in the table below. 

Installation of fire damper into flexible 

building elements (gypsum board walls 

or similar) with fire classification EI 60 

(Fig. 2 and Fig. 3)

1.  Installation opening in the flexible wall must comply with 

the dimensions given in the table below. 

2.  The fire damper blade must be closed during installation.  

NOTE! The blade supports may not be removed  

before completed grouting.

3.  Place the fire damper centrally in the opening. Fire 

damper positioning: 
a.  The fire damper must be placed so that the blade is cen-

trally inside the opening in the intermediate floor or wall.

b.  The marking (1) on the actuator side shall align with 

the building element surface.

c.  The damper axle can be placed in any position (Ø100 

- Ø400) or in horizontal position when mounted in the 

wall (Ø500 - Ø1000).

4.  Support the damper properly in the opening.  Fasten the 

damper with the angle brackets (2), 1-4 pcs depending 

on damper size. Use Ø5 mm screws suitable for rigid 

construction to lock the position. 

5.  Completely fill the gap M between the damper and the 

building element using incombustible, rock based, fine-

grained gypsum or concrete cast. Protect the damper 

whilst infilling. 

6.  Remove the blade supports (4) when finished grouting 

(Ø500 - Ø1000).

2.  The fire damper blade must be closed during installa-

tion.  NOTE! The blade supports may not be removed  

before completed grouting.

3.  Place the fire damper centrally in the opening. Fire 

damper positioning: 
a.  The fire damper must be placed so that the blade is 

centrally inside the opening in the wall.

b.  The marking (1) on the actuator side shall align with 

the building element surface.

c.  The damper axle can be placed in any position (Ø100 

- Ø400) or in horizontal position when mounted in the 

wall (Ø500 - Ø1000).

4.  Support the damper properly in the opening. Fasten the 

damper with the angle brackets (2), 1-4 pcs depending 

on damper size. Use Ø5 mm screws or anchors suitable 

for flexible construction to lock the position.

5.  Completely fill the gap S between the fire damper and 

the wall opening on both sides by using fire-resistant 

mass, e.g. Silacoll 100. The depth of the filling must cov-

er the total thickness of the boards (Figure 3). 

6.  Remove the blade supports (4).

7.  Check the functioning of the fire damper and proper move-

ment of the blade. Clean the damper, if necessary. Place 

plastic covers on the openings and keep them covered, until 

ducts are connected to the damper.

8.  To reset the fuse mechanism: Turn the handle towards the 

OPEN position until the mechanism clicks and the blade 

locks into position. 

9.  Manual function testing of the motorized fire damper can be 

performed with the tool delivered with the  

actuator. When connected to a power supply, function testing 

is done by using the switch of the thermal trip (3). NOTE! If 

you open the damper blade manually with the tool, be sure 

to release the damper back to the closed position before 

switching on power.

10. Connect ducts to the damper according to the instructions 

provided by the designer and the manufacturer.  Access 

panel should be placed next to the fire damper to enable 

necessary cleaning and inspection.  Suspend the ducts 

according to instructions from the manufacturer and ensure 

that the ductwork does not cause any load on the damper 

installation.

11. If the fire damper is used as an air transfer or air terminal 

device, it must be equipped with a protective grille. The dis-

tance between the grille and the damper blade in the open 

position must be at least 30 mm. In case of large fire damp-

ers, an extension piece must be installed between the grille 

and the damper blade. A circular duct of suitable length can 

be used as an extension piece.

12. When dampers are to be mounted next to one another, the 

distance between the dampers should be 

200 mm (Fig. 4).

Содержание ETCE

Страница 1: ...INSTRUCTIONS FOR INSTALLATION OPERATION AND MAINTENANCE Fire Damper ETCE and ETCS...

Страница 2: ......

Страница 3: ...et the mechanism turn the handle until the mechanism clicks The function testing interval is always determined separately for each building but testing must be carried out at least twice a year accord...

Страница 4: ...enance 4 Installation into building elements with fire classification EI 60 100 1000 M S 1 2 1 t t D D 3 3 4 4 2 Figure 1 500 1000 Remove the blade supports when installation is finalized Figure 2 Fig...

Страница 5: ...damper centrally in the opening Fire damper positioning a The fire damper must be placed so that the blade is centrally inside the opening in the wall b The marking 1 on the actuator side shall align...

Страница 6: ...igure 6 Figure 8 Figure 7 min 200 mm 200 mm t M 2 1 3 4 M M S 1 1 t t D D 4 4 3 5 5 2 2 3 t mm EI 90 S 126 EI 120 S 126 t mm EI 90 S 110 EI 120 S 110 t mm 100 400 500 1000 EI 90 S 120 140 EI 120 S 120...

Страница 7: ...ve the blade supports 4 when finished grouting 500 1000 2 The fire damper blade must be closed during installation NOTE The blade supports may not be removed before completed grouting 3 Place the fire...

Страница 8: ...nually with the tool be sure to release the damper back to the closed position before switching on power 10 Connect ducts to the damper according to the instruc tions provided by the designer and the...

Страница 9: ...d proper indication verified Electric specification Operating temperature 25 C 70 C 230 VAC 1 5 A max 1 Test button 2 Cover 3 Screws 4 Microswitch under cover 5 Handle Fire damper blade position open...

Страница 10: ...re 10 2 Remove the cover 2 and the two screws 3 Figure 11 3 Remove the microswitch 4 screws Figure 12 4 Turn the switch 4 over to the position shown in Fig 13 and fasten it with the screws 5 NOTE As t...

Страница 11: ...14 2 Remove the fuse part mounting screw 6 Figure 15 3 Holding the test button pull out the complete fuse part 7 Figure 16 4 Correctly install the new fuse part and fasten it with the screw 6 5 Test...

Страница 12: ...area We offer our customers innovative technologies high quality and outstanding performance supported by more than a century of accumulated industry experience The widest product range in the market...

Отзывы: