Installation
CAIR
fricostar
®
42
FläktGroup DC-2009-0019-GB 2018-01/R9 • Specifications are subject to alteration without notice
Example 3
Fig. 6-5:
Circuit with pool water condenser and parallel filter circuit with only one pool water
inlet and outlet.
Follow the procedure specified in example 3:
•
Electrical interlock of the filter pump with the pool water condenser pump to be
completed by others on site.
•
In addition non-return dampers or non-return valves must be installed.
Example 4
Fig. 6-6:
Circuit with pool water condenser integrated in filter circuit bypass
Follow the procedure specified in example 4:
•
Both the filter unit and the CAIR
fricostar
unit must regulate the pump.
•
A parallel solenoid valve must be installed and regulated (instead of control output
for PWC pump). If required, additional contacts to be provided by others on site.
•
Install a throttle valve for regulating the water volume.
6
5
1
6
2
4
3
1: Pump
2: Filter
3: Pool water condenser
4: Temperature sensor
5: Filter circuit pump
6: Non-return damper
6
4
2
5
1
7
3
1: Solenoid valve
2: Pre-filter
3: Pool water condenser
4: Temperature sensor
5: Filter circuit pump
6: Throttle valve
7: Flow meter
NOTICE!
Consider the maximum possible water flow rate in the circuit for pool water con-
denser. Refer to order-related unit documentation for technical data and specifica-
tions.