STRA-04 Room controller. Installation and maintenance manual.

STRA-04 for Optivent

Fläkt Woods

8

Specifications are subject of alteration without further notice.

CO 

2

 control (P control)

Fläkt Woods STRZ-18-1 is an active CO 

2

 sensor

(0-10V)and is activated in room controller by setting

parameter 81 to 5. When the controller exceeds the CO 

2

value (parameter 112 FS =500 ppm), it starts controlling

against a fully open damper (UO3). The damper opens

fully at Parameter 113 (FS=1000 ppm). Heating/Cooling

(PI) in controlled concurrently with the CO 

2

 control.

If heating is required, the heating signal increases on

heating output UO1.

Window contact

When the window contact has been configured, the

regulator is set to normal operation when the window is

closed. When the window is open, the controller goes into

Off mode, the heating and cooler outputs are set to 0 V

and the frost protection function is activated.

Frost protection

STRA-04 has built-in frost protection, which is activated

when the controller is not in use. The frost protection

prevents the temperature from dropping below 8°C. The

fan speed and controls automatically return to normal

when the frost protection is deactivated.

Control the light with an occupancy sensor

It’s possible to control the operation of the light with

an occupancy sensor through a relay and its socket

(STRZ-73-b). The light will switch off when the room

is unoccupied. The socket for wiring is screwless quick

connection.
Parameter 60 should be changed to 1 when using this

function.

Wiring diagram

Parameter settings

STRA-04 is delivered with a number of factory settings.

To achieve the desired function, the controller must

be adapted to its application. This is done via the

parameter menu in the display. The applications can vary

dramatically, and incorrectly set parameters can impair

the controller's and application's function. For this reason,

make sure you set the parameters that are critical to your

particular application. If in doubt, contact Fläkt Woods

TSS Controls.

Parameter menu

In STRA-04, various parameter values can be set in a

parameter menu. This parameter menu is accessed by

simultaneously pressing the INCREASE and DECREASE

buttons for about 5 seconds until the Service indication

lights up in the display. After this, press the INCREASE

button twice.
Initially, the parameter menu will only show a parameter

number (P01, P02, P03 etc.). You can scroll between the

parameters by pressing the INCREASE and DECREASE

buttons. When the right parameter has been selected,

press the Function button. The parameter value will be

shown and the parameter number will disappear.
The parameter value can now be changed with the

INCREASE and DECREASE buttons. When the

INCREASE and DECREASE buttons are held pressed

down, the value in the display will start scrolling, first

slowly and then with increasing speed, in about 3-4 steps

with roughly 2-3 seconds between the steps.

Confirm/Reject

To confirm the changed parameter, press the Function

button again. The display will return to showing the

parameter number. Before confirming the change, you can

retrieve the original value (the value that was displayed

before you made the change) by simultaneously pressing

the INCREASE and DECREASE buttons. The original

value will be shown on the display.

Return

After about 1 minute, or when the INCREASE and

DECREASE buttons are pressed simultaneously while

you are in the menu, the display will return to normal.

The word Exit will appear in the display after the last

parameter. By pressing the Function button when Exit

appears, you can exit the parameter menu. If you press

INCREASE, you reach the first parameter. If you press

DECREASE, you reach the last parameter.

8790 GB 2016.03

8790 GB 2016.03

Содержание STRA-04

Страница 1: ...ations are subject of alteration without further notice Contents STRA 04 for Optivent Installation instructions 2 Controller 3 Display handling 3 Technical data 4 Configuration 4 Operating modes 6 Control 7 Condensation detector Window contact Frost protection 8 Parameter settings 9 Function key 11 ...

Страница 2: ...thout further notice STRA 04 for Optivent Installation instructions Follow local safety regulations when installing the product For information on putting the product into operation see the manual STRA Manual which can be downloaded from www flaktwoods com 1 2 3 or 4 5 Dimensions Dimensions given in mm 8790 GB 2016 03 ...

Страница 3: ... press down to the minimum limit FS 3 Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Function button If the Function button is pressed briefly less than 5 seconds when the controller STRA 04 is in the Preset operating mode Parameter 45 FS 3 Occupied the controller switches to the Bypass operating mode If the ...

Страница 4: ...al room sensor PT1000 sensor 0 50 C A suitable sensor is Fläkt Woods STRZ 05 Occupancy detector Closing potential free contact A suitable occupancy detector is Fläkt Woods STRZ 09 CO 2 sensor STRZ 18 1 1 CO 2 sensor 0 10V Outputs Forced ventilation 24 V AC actuator max 0 5 A Valve actuator thermal actuator or Optivent 2 outputs Valve actuator 0 10 V DC max 5 mA Thermal actuator 24 V AC max 2 0 A C...

Страница 5: ...cted to terminals 10 and 11 Make sure that the reference pole G0 is connected to the correct terminal on the actuator alternatively For 24 V AC thermal actuator max 2 0 A The thermal actuator is connected between terminals 24 and 20 GDO 30 Al1 For external room sensor PT1000 Measuring range 0 50 C Connect sensor between terminal 30 and 41 AGnd 31 AI2 For 0 10V CO 2 sensor input signal 32 DI1 Occup...

Страница 6: ... For further information see Occupancy Control section Occupied The Occupied operating mode means that the room is in use and is adjusted according to Comfort mode The controller adjusts the room temperature around a heating setpoint and a cooling setpoint Parameters 1 and 2 FS heating setpoint 22 C cooling setpoint 24 C The setpoint values can also be locally adjusted 3 C via the display on the u...

Страница 7: ... the function illustrated in the picture above where the activated occupancy detector shifts to the Occupied operating mode When the occupancy sensor is deactivated the controller returns to the Unoccupied operating mode to save energy Control STRA 04 can be configured for different control states control sequences Parameter 11 FS 4 Heating Cooling with VAV control and forced supply air function H...

Страница 8: ...ions can vary dramatically and incorrectly set parameters can impair the controller s and application s function For this reason make sure you set the parameters that are critical to your particular application If in doubt contact Fläkt Woods TSS Controls Parameter menu In STRA 04 various parameter values can be set in a parameter menu This parameter menu is accessed by simultaneously pressing the...

Страница 9: ...igital 2 Forced Vent 3 Step Analog 3 None 4 Ordinary Analog output 5 None 6 Control of EC fan 1 24 UO3 output in manual mode N A 0 28 Actuator type for UO3 0 0 10v 1 2 10v 2 10 2v 3 10 0v 1 29 Heating Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 30 Cooling Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 31 Heating Thermal Actuator Time N A Seconds 60 32 Cooling Therm...

Страница 10: ...Cooling 0 Not Available 1 Available 0 76 Forced Ventilation control mode 0 No Action 1 Forced on Heat Cool output at 100 2 Forced on Cool output at 100 2 77 P I R Activated Operation Mode 3 Occupied 4 Bypass 3 78 The Controller PLA Address Used in EXOline Set by Production 79 The Controller ELA Address Used in EXOline Set by Production 80 Cool output 0 For N C actuator 1 For N O actuator 0 81 AI2 ...

Страница 11: ...100 cooling N A 305 Max air level at 100 CO2 N A 306 Air level at Off Unoccupied Standby N A N A 307 Air level at Occupied mode N A N A 308 Air level Boost mode Button only N A N A 309 Free Cooling 0 Not Available 1 Available See 75 322 Type of STRA 0 STRA 04 1 STRA 14 Set by production 323 The floor the STRA is placed at 9999 Not Used in IPSUM 0 324 The room the STRA is placed 9999 Not Used in IP...

Страница 12: ...he function key toggles between forced supply air and normal operation Forced supply air is indicated by this symbol 2 A long pressure over 5 seconds on the function key shuts the controller off i e it goes into sleep mode The background lighting on the screen is shut down 3 A new brief pressure re starts the controller and it goes initially to forced supply air 8790 GB 2016 03 ...