STRA-04 Room controller. Installation and maintenance manual.

STRA-04 for Optivent

Fläkt Woods

6

Specifications are subject of alteration without further notice.

Operating modes

STRA-04 has five operating modes. The Function button

can be used to switch between three of them. These

operating modes can be set via the parameter menu

(parameter 45) in the display. Occupied is the preset

operating mode.

Off

Operating mode Off means that the controller is inactive

(heat and cooling are disconnected). However, the

temperature must not drop below the set minimum

temperature (parameter 6, FS=8°C). If the room

temperature drops below the minimum temperature, the

controller will start heating.
On the display, the background lighting is not lit, and

only OFF is shown.

Unoccupied

The Unoccupied operating mode is an energy-saving

mode. This means that the room controlled by the

controller is currently not in use, or is not used for long

periods, e.g. during evenings, nights, weekends or by non

presence when using occupancy sensor. Both heating and

cooling are disconnected within a temperature interval

with adjustable min./max. temperatures (Parameters 4

and 5, FS min=19°C, max=27°C).
The background lighting is not lit on the display, but the

current room temperature (or setpoint, depending on the

configuration) is shown. OFF is shown on the display in

this case too.

Stand-by

The Stand-by operating mode means that the room is in

energy save mode and not currently in use, e.g. during

nights, weekends or evenings. This mode is currently not

used by default settings from Factory but it can be used

instead of unoccupied mode by non presence when using

occupancy sensor. The room temperature is controlled

around the applicable heating and cooling setpoints with

an extended temperature interval (FS = +/-3°C).
For example, if the heating setpoint is 22°C and the

cooling setpoint is 24°C, the controller will allow a

room temperature between 19°C and 27°C. In addition,

the setpoint values can be locally ad/- 3°C via

a setpoint knob or via the display on the room unit.

Display: background lighting is lit (dimmed) and

STANDBY, and current room temperature (or setpoint,

depending on configuration) is shown on the display. For

further information, see Occupancy Control section.

Occupied

The Occupied operating mode means that the room is

in use and is adjusted according to Comfort mode. The

controller adjusts the room temperature around a heating

setpoint and a cooling setpoint (Parameters 1 and 2,

FS heating setpoint=22°C, cooling setpoint=24°C). The

setpoint values can also be locally ad/- 3°C via the

display on the unit, or via a central command.

On the display, the background lighting is lit (dimmed)

and the occupancy indicator is lit (see Display Handling

section). The current room temperature (or setpoint

depending on the configuration) is shown.

Bypass

The Bypass operating mode means that the controller

adjusts the room temperature in the same way as in the

Occupied mode. The output for forced ventilation is also

activated (10V cooling output UO2). After a configurable

time (Parameter 12, FS=60 minutes), the controller

automatically returns to Preset mode. Bypass is normally

activated by pressing the Function button, the occupancy

detector (depending on the configuration), or via a central

command. This operating mode is useful in conference

rooms where many people are present simultaneously for

a limited period of time.
The background lighting on the display is lit (dimmed).

The occupancy detector and the symbol for forced

ventilation are lit (see Display Handling section). The

current room temperature (or setpoint, depending on the

configuration) is shown.

Activation operating modes

Preset operating mode

Occupied is the preset operating mode. The desired

operating mode is configured in the parameter menu on

the display (parameter 45). The operating mode in the

room controller is changed if the following commands/

events occur:
• When the Function button is pressed
• When the occupancy detector is activated/deactivated
• When the CO value on the 

2

 analogue input is exceeded

• If central control is used, e.g. central time control or

central booking system.

Function button

Bypass

(Forced ventilation)

Button/Timer

Occupied

(Preset operating mode)

Shutdown

(Unoccupied)

> 5 s

Shutdown (Off or Unoccupied)

If the Function button is pressed and held for more than

5 seconds, the controller switches to Shutdown mode,

which may be Off or Unoccupied regardless of the current

operating mode The activated operating mode, Off or

Unoccupied, is configured via the display. The factory

configuration is Unoccupied.

8790 GB 2016.03

8790 GB 2016.03

Содержание STRA-04

Страница 1: ...ations are subject of alteration without further notice Contents STRA 04 for Optivent Installation instructions 2 Controller 3 Display handling 3 Technical data 4 Configuration 4 Operating modes 6 Control 7 Condensation detector Window contact Frost protection 8 Parameter settings 9 Function key 11 ...

Страница 2: ...thout further notice STRA 04 for Optivent Installation instructions Follow local safety regulations when installing the product For information on putting the product into operation see the manual STRA Manual which can be downloaded from www flaktwoods com 1 2 3 or 4 5 Dimensions Dimensions given in mm 8790 GB 2016 03 ...

Страница 3: ... press down to the minimum limit FS 3 Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requirement Function button If the Function button is pressed briefly less than 5 seconds when the controller STRA 04 is in the Preset operating mode Parameter 45 FS 3 Occupied the controller switches to the Bypass operating mode If the ...

Страница 4: ...al room sensor PT1000 sensor 0 50 C A suitable sensor is Fläkt Woods STRZ 05 Occupancy detector Closing potential free contact A suitable occupancy detector is Fläkt Woods STRZ 09 CO 2 sensor STRZ 18 1 1 CO 2 sensor 0 10V Outputs Forced ventilation 24 V AC actuator max 0 5 A Valve actuator thermal actuator or Optivent 2 outputs Valve actuator 0 10 V DC max 5 mA Thermal actuator 24 V AC max 2 0 A C...

Страница 5: ...cted to terminals 10 and 11 Make sure that the reference pole G0 is connected to the correct terminal on the actuator alternatively For 24 V AC thermal actuator max 2 0 A The thermal actuator is connected between terminals 24 and 20 GDO 30 Al1 For external room sensor PT1000 Measuring range 0 50 C Connect sensor between terminal 30 and 41 AGnd 31 AI2 For 0 10V CO 2 sensor input signal 32 DI1 Occup...

Страница 6: ... For further information see Occupancy Control section Occupied The Occupied operating mode means that the room is in use and is adjusted according to Comfort mode The controller adjusts the room temperature around a heating setpoint and a cooling setpoint Parameters 1 and 2 FS heating setpoint 22 C cooling setpoint 24 C The setpoint values can also be locally adjusted 3 C via the display on the u...

Страница 7: ... the function illustrated in the picture above where the activated occupancy detector shifts to the Occupied operating mode When the occupancy sensor is deactivated the controller returns to the Unoccupied operating mode to save energy Control STRA 04 can be configured for different control states control sequences Parameter 11 FS 4 Heating Cooling with VAV control and forced supply air function H...

Страница 8: ...ions can vary dramatically and incorrectly set parameters can impair the controller s and application s function For this reason make sure you set the parameters that are critical to your particular application If in doubt contact Fläkt Woods TSS Controls Parameter menu In STRA 04 various parameter values can be set in a parameter menu This parameter menu is accessed by simultaneously pressing the...

Страница 9: ...igital 2 Forced Vent 3 Step Analog 3 None 4 Ordinary Analog output 5 None 6 Control of EC fan 1 24 UO3 output in manual mode N A 0 28 Actuator type for UO3 0 0 10v 1 2 10v 2 10 2v 3 10 0v 1 29 Heating Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 30 Cooling Modulating Actuator Control 0 0 10v 1 2 10v 2 10 2v 3 10 0v 0 31 Heating Thermal Actuator Time N A Seconds 60 32 Cooling Therm...

Страница 10: ...Cooling 0 Not Available 1 Available 0 76 Forced Ventilation control mode 0 No Action 1 Forced on Heat Cool output at 100 2 Forced on Cool output at 100 2 77 P I R Activated Operation Mode 3 Occupied 4 Bypass 3 78 The Controller PLA Address Used in EXOline Set by Production 79 The Controller ELA Address Used in EXOline Set by Production 80 Cool output 0 For N C actuator 1 For N O actuator 0 81 AI2 ...

Страница 11: ...100 cooling N A 305 Max air level at 100 CO2 N A 306 Air level at Off Unoccupied Standby N A N A 307 Air level at Occupied mode N A N A 308 Air level Boost mode Button only N A N A 309 Free Cooling 0 Not Available 1 Available See 75 322 Type of STRA 0 STRA 04 1 STRA 14 Set by production 323 The floor the STRA is placed at 9999 Not Used in IPSUM 0 324 The room the STRA is placed 9999 Not Used in IP...

Страница 12: ...he function key toggles between forced supply air and normal operation Forced supply air is indicated by this symbol 2 A long pressure over 5 seconds on the function key shuts the controller off i e it goes into sleep mode The background lighting on the screen is shut down 3 A new brief pressure re starts the controller and it goes initially to forced supply air 8790 GB 2016 03 ...

Отзывы: