Note
For intrinsically safe applications, the LCP200 forms an intrinsically safe explosion protection system when used with intrinsically
safe associated apparatus (a barrier) or with any other intrinsically safe devices.
The following requirements must be met: Uo ≤ Ui , Io ≤ Ii, Po ≤ Pi , Co ≥ Ci + Cc, Lo ≥ Li + Lc.
When installing the terminal cover, use a 4 mm hex key to tighten the screws evenly in a criss‐cross pattern, such as
the one indicated in figure 4, to a torque of 8.7 N•m (77 lbf•in) +/- 10%, to help ensure the cover is properly installed.
Apply silicone lubricant to the terminal box O-ring (key 7, figure 10).
Figure 4. Proper Cover Installation
NOTE: TIGHTEN THE SCREWS IN A CRISS‐CROSS PATTERN
TO HELP ENSURE PROPER COVER INSTALLATION.