Instruction Manual
D104296X012
LCP200 Local Control Panel
August 2018
11
Figure 7. Wiring Diagram 2, 24 VDC External Power Configuration, Point-to-Point
GG22618 SHEET 4
LOGIC SOLVER
(USER SUPPLIED)
NOTES:
1 OPTIONAL CABLING TO RESET, TRIP, AND TEST CONTACTS. SHOWN ABOVE IS CABLING TO
1
RESET CONTACT.
2 CONNECT EITHER NO-C OR NC-C TERMINALS OF RESET, TRIP AND TEST CONTACTS. SHOWN
1
ABOVE IS RESET NO-C TERMINALS.
3 USE METAL CONDUIT FOR CABLING BETWEEN DVC6200 SIS AND LCP200 AS EMI SHIELD.
4 THE DIGITAL INPUT DOES NOT NEED TO BE CONNECTED FOR THE LCP200 TO OPERATE.
LCP200
3
1
DVC6200 SIS
TERMINAL BOX
DIGITAL IN
24 VDC
SOURCE
2
(USER SUPPLIED)
OUTPUT
4-20 mA
TALK
AUX LOOP
OUT
CAL
AUX LOOP
DVC6200 SIS
TEST
TRIP
NOT
AVAILABLE
RESET
POWER
24V
4