Error rotor position protection of compressor
P4
☆
5
Mode conflict
P5
☆
6
Low pressure protection of compressor
P6
☆
7
O (on) X(off)
☆
(flash at 2Hz)
10.2
Outdoor unit error code explanation:
Display LED
STATUS
E0
Outdoor EEPROM malfunction
E2
Indoor / outdoor units communication error
E3
Communication malfunction between IPM board and outdoor main board
E4
Open or short circuit of outdoor unit temperature sensor
E5 Voltage
protection
E8
Outdoor fan speed has been out of control
F1
No A Indoor unit coil outlet temperature sensor or connector of sensor is defective
F2
No B Indoor unit coil outlet temperature sensor or connector of sensor is defective
F3
No C Indoor unit coil outlet temperature sensor or connector of sensor is defective
F4
No D Indoor unit coil outlet temperature sensor or connector of sensor is defective
F5
No E Indoor unit coil outlet temperature sensor or connector of sensor is defective
P1
High pressure protection (For
P2 Low pressure protection (For
P3
Current protection of compressor
P4
Temperature protection of compressor discharge
P5
High temperature protection of condenser
P6
IPM module protection
LP
Low ambient temperature protection
Note: Once these error codes display, they will disappear in at least 30 seconds if the unit come back to
normal.(Except E2&E3)
FS4MIF-281AE2
FS4MIF-361AE2
FS5MIF-421AE0)
FS4MIF-281AE2
FS4MIF-361AE2
FS5MIF-421AE0
)
Содержание FS2MIF-141AE2
Страница 8: ...5 Wiring diagram FS2MIF 141AE2 FS2MIF 181AE2 FS3MIF 211AE2 FS3MIF 271AE2 8 ...
Страница 9: ...FS4MIF 281AE2 FS4MIF 361AE2 9 ...
Страница 10: ...FS5MIF 421AE0 10 ...
Страница 33: ...9 3 1 2 Indoor outdoor units communication error ...
Страница 41: ...9 3 3 2 Communication malfunction between IPM board and outdoor main board ODU E3 ...
Страница 44: ...9 3 3 5 High pressure protection ODU P1 For FS4MIF 281AE2 FS4MIF 361AE2 FS5MIF 421AE0 ...
Страница 46: ...9 3 3 7 Current protection of compressor ODU P3 ...