9.3.3.10 IPM module protection (ODU P6)
IPM
module
protection
Check
whether
the
voltage
range
of
P
‐
N
on
IPM
module
is
normal?
DC277
‐
356V
for
18
‐
28KBtu/h;
DC277
‐
410V
for
36
‐
42KBtu/h
Yes
Yes
No
Yes
Check
whether
the
input
power
supply
is
correct?
208
‐
230V,
1N,
60Hz
No
No
Regulate
it
to
correct,
then
check
whether
the
system
can
work
normally?
Check
whether
the
power
supply
line
is
connected
correctly
and
tightly
Yes
Connect
it
correctly
and
tightly,
check
ok
or
not?
No
Check
whether
the
connecting
line
between
main
board
and
the
IPM
module
is
connected
tightly
Yes
Connect
it
tightly,
check
ok
or
not?
No
No
No
Connect
it
well,
check
ok
or
not?
Check
whether
the
connecting
line
of
the
compressor
is
connected
correctly
or
tightly
Replace
the
IPM
module,
check
whether
the
system
can
work
normally?
No
No
Replace
the
main
board;
check
whether
the
system
can
work
normally?
No
Replace
the
compressor,
check
whether
the
system
can
work
normally?
Check
whether
the
lines
in
E
‐
part
box
are
connected
tightly
Yes
Connect
it
tightly,
check
ok
or
not?
No
No
Yes
No
Replace
the
bridge
rectifiers
Check
whether
the
bridge
rectifiers
are
normal?
Use
the
multimeter
to
measure
the
resistance
between
each
two
terminals,
check
whether
there
is
the
condition
that
value
of
resistance
is
0
Check
whether
the
connecting
line
of
every
reactor
is
normal?
If
the
line
is
broken,
the
resistance
of
the
two
ports
is
∞
(
models
except
for
Check
whether
the
PFC
module
broken
(for
Replace
the
connecting
line
or
reactor
or
replace
the
PFC
module(for
Yes
No
No
Yes
Trouble
is
solved
Check
if
the
outdoor
fan
runs
properly
or
the
outdoor
unit
ventilation
is
good.
No
Check
whether
the
resistance
of
the
fan
motor
is
normal.
If
not,
replace
the
fan
motor.
For
other
models,
r
efer
to
the
solution
of
fan
speed
has
been
out
of
control
malfunction
.
F i n d
o u t
the
cause
and
have
it
solved.
Yes
Yes
Yes
FS4MIF-281AE2
FS4MIF-361AE2
FS5MIF-421AE0)
FS4MIF-361AE2
FS5MIF-421AE0)
FS4MIF-281AE2
FS4MIF-361AE2
FS5MIF-421AE0)
Содержание FS2MIF-141AE2
Страница 8: ...5 Wiring diagram FS2MIF 141AE2 FS2MIF 181AE2 FS3MIF 211AE2 FS3MIF 271AE2 8 ...
Страница 9: ...FS4MIF 281AE2 FS4MIF 361AE2 9 ...
Страница 10: ...FS5MIF 421AE0 10 ...
Страница 33: ...9 3 1 2 Indoor outdoor units communication error ...
Страница 41: ...9 3 3 2 Communication malfunction between IPM board and outdoor main board ODU E3 ...
Страница 44: ...9 3 3 5 High pressure protection ODU P1 For FS4MIF 281AE2 FS4MIF 361AE2 FS5MIF 421AE0 ...
Страница 46: ...9 3 3 7 Current protection of compressor ODU P3 ...