R32 ATW Service Manual
61
When the unit is set combination mode and the unit is running one mode
a)
In main interface, short press
or
, to enter current running mode temperature
setting interface, one digital tube flashes. (no operation for 5 seconds to exit setting)
b)
Press
or
button to choose the target temperature. Press button once to increase the
setting temperature by 1°C. When the setting temperature reaches the highest or lowest value,
press the button again that the setting temperature won’t change.
c)
Short press
button, to enter the other mode temperature setting interface.
d)
After finishing the setting, Press
button or no operation for 5 seconds, it will save the
setting and exit the temperature setting interface.
2. When the unit is without DHW mode
a)
In main interface, short press
or
, to enter heating/cooling water temperature T
S1
setting interface, middle digital tube flashes.
b)
Press
or
button to choose the target temperature. Press button once to increase the
setting temperature by 1°C. When the setting temperature reaches the highest or lowest value,
press the button again that the setting temperature won’t change.
c)
Press
button or no operation for 5 seconds, it will save the setting and exit the temperature
setting interface.
Notes: 1. The default temperature is 7
℃
for cooling mode, 45
℃
for heating mode, 50
℃
for DHW
mode.
2. The setting temperature range is 5~25
℃
for cooling mode, 25~60
℃
for heating mode and
40~60
℃
for DHW mode.
13.4 Display shows
13.4.1 Digital display
Status
DHW mode is ON
*
DHW mode is OFF
*
Standby
mode
Running
heating/cooling mode
Running DHW
mode
Setting
temperature
All modes
Left digital
T1
T1
T
S1
T
S1
T1
Middle digital
T7
T
S2
T7
T
S2
T
S1
Note:
T1: water outlet temperature of hydronic module
T7: DHW water tank temperature
T
S1
: heating or cooling mode setting temperature
T
S2
: DHW mode setting temperature
*: When SW2_4 is in OFF position, DHW mode is ON; when SW2_4 is in ON position, DHW mode is
OFF.
13.4.2 Icon display
When there is a box outside the mode icon, it means the unit is running in this mode.
Содержание FHIF-WHS-120CE3
Страница 2: ......
Страница 9: ...R32 ATW Service Manual 7 1 2 2 Hydronic module FHIF WHS 120CE3 FHIF WHS 160CE3...
Страница 18: ...R32 ATW Service Manual 16 Pic 4 3 Domestic hot water mode operation range...
Страница 23: ...R32 ATW Service Manual 21 8 System diagram...
Страница 24: ...R32 ATW Service Manual 22 9 Wiring diagram 9 1 Outdoor unit 9 1 1 9 1 2 FHOF WHS 100CE3 FHOF WHS 160CE3 3F...
Страница 28: ...R32 ATW Service Manual 26 Main PCB 3 Hydronic module Main PCB...
Страница 29: ...R32 ATW Service Manual 27 Filter board...
Страница 34: ...R32 ATW Service Manual 32 Model FHOF WHS 160CE3 3F...
Страница 35: ...R32 ATW Service Manual 33 Single unit installation More than one unit installation Unit mm...
Страница 46: ...R32 ATW Service Manual 44 HEATING MODE COOLING MODE...
Страница 47: ...R32 ATW Service Manual 45 HEATING MODE WITHOUT COOLING MODE DHW MODE WITHOUT COOLING MODE...
Страница 48: ...R32 ATW Service Manual 46 HEATING MODE WITHOUT DHW MODE AND DHW TANK ONLY DHW MODE...
Страница 56: ...R32 ATW Service Manual 54 When the unit has error code alarm port has a 220V output...
Страница 59: ...R32 ATW Service Manual 57...