Attention
In order to prevent oxidation inside the copper tube during copper pipe welding, nitrogen filling must be taken.
Otherwise the scale will block the refrigeration system!
11.3.2 Connection between outdoor unit and hydronic module
Note: The refrigerant circuit of the hydraulic module contains a small amount of Nitrogen, which is used to keep
the pressure and detect leakage. When installing, unscrew the nut of the refrigerant pipe joint of the hydraulic
module. If there is no gas flowing out, check the refrigerant circuit of the unit for leakage. Install and operate only
after confirming no leakage.
11.3.3 Accessory pipe in pipeline
Because of different mounting positions of the air conditioning, the required accessory pipe can be long or short,
to avoid affecting the capacity from too long cooling pipe, please select a reasonable tube length according to table
below, try to select the location of the shorter lines for the installation.
(1)
The maximum allowable operating distance away from the pipe.
<6.5kW
6.5~10.5kW
≥
10.5kW
Pipe length
Max. length 15m
Max. length 20m
Max. length 50m
Height difference
Max. height 8m
Max. height 10m
Max. height 20m
Oil return bends quantity
Up to 10
Up to 10
Up to 15
Note: On condition that 80% of the cooling capacity is guaranteed in the above parameters, the cooling capacity
loss and return oil has been fully considered
.
(2)
The use of oil return bend.
When the height difference between the indoor and outdoor unit is greater than 5 m, in order to facilitate oil
return of the compressor, oil return bend must be used. Upon site operations, the following typical installation
methods can be referred to.
Содержание FHIF-WHS-120CE3
Страница 2: ......
Страница 9: ...R32 ATW Service Manual 7 1 2 2 Hydronic module FHIF WHS 120CE3 FHIF WHS 160CE3...
Страница 18: ...R32 ATW Service Manual 16 Pic 4 3 Domestic hot water mode operation range...
Страница 23: ...R32 ATW Service Manual 21 8 System diagram...
Страница 24: ...R32 ATW Service Manual 22 9 Wiring diagram 9 1 Outdoor unit 9 1 1 9 1 2 FHOF WHS 100CE3 FHOF WHS 160CE3 3F...
Страница 28: ...R32 ATW Service Manual 26 Main PCB 3 Hydronic module Main PCB...
Страница 29: ...R32 ATW Service Manual 27 Filter board...
Страница 34: ...R32 ATW Service Manual 32 Model FHOF WHS 160CE3 3F...
Страница 35: ...R32 ATW Service Manual 33 Single unit installation More than one unit installation Unit mm...
Страница 46: ...R32 ATW Service Manual 44 HEATING MODE COOLING MODE...
Страница 47: ...R32 ATW Service Manual 45 HEATING MODE WITHOUT COOLING MODE DHW MODE WITHOUT COOLING MODE...
Страница 48: ...R32 ATW Service Manual 46 HEATING MODE WITHOUT DHW MODE AND DHW TANK ONLY DHW MODE...
Страница 56: ...R32 ATW Service Manual 54 When the unit has error code alarm port has a 220V output...
Страница 59: ...R32 ATW Service Manual 57...