R32 ATW Service Manual
5
electrical contact between equipment and building is allowed. Insulator must be installed in between.
30.
Any work carried out on the Indoor Unit / Outdoor Unit after removing any panels which is secured by screws, must be carried out
under the supervision of authorized dealer and licensed installation contractor.
This unit must be properly earthed. The electrical earth must not be connected to a gas pipe, water pipe, the earth of lightening rod or
31. a telephone. Otherwise there is a danger of electrical shock in the event of an insulation breakdown or electrical earth fault in the
outdoor unit.
Do not use joint cable for outdoor connection cable. Use specified outdoor connection cable, refer to instruction
CONNECT THE
32.
CABLE TO THE OUTDOOR UNIT
and connect tightly for outdoor connection. Clamp the cable so that no external force will be acted
on the terminal. If connection or fixing is not perfect, it will cause heat up or fire at the connection.
CAUTION
1.
Do not install the Indoor Unit / Outdoor Unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates
at surrounding of the unit, it may cause fire.
2.
Do not release refrigerant during piping work for installation, re-installation and during repairing a refrigeration parts. Take care of the
liquid refrigerant, it may cause frostbite.
3. Do not install this appliance in a laundry room or other high humidity location. This condition will cause rust and damage to the unit.
4. Make sure the insulation of power supply cord does not contact hot part (i.e. refrigerant piping) to prevent from insulation failure (melt).
5.
Do not apply excessive force to water pipes that may damage the pipes. If water leakage occurs, it will cause flooding and damage to
other properties.
6. Do not touch the sharp aluminum fin, sharp parts may cause injury.
7.
Do not release refrigerant into the atmosphere. The product contains fluorinated greenhouse gases and that its functioning relies upon
such gases.
8. Select an installation location which is easy for maintenance.
9.
Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage
the furniture.
Power supply connection to Indoor Unit.
Power supply point should be in easily accessible place for power disconnection in case of emergency.
Must follow local national wiring standard, regulation and this installation instruction.
Strongly recommended to make permanent connection to a circuit breaker.
10.
-
Power supply 1: Use approved 20A 4-poles circuit breaker with a minimum contact gap of 3.0 mm.
-
Power supply 2: Use approved 15/16A 2-poles circuit breaker with a minimum contact gap of 3.0 mm. (Only applicable for
S*C09*3E8)
or
Use approved 20A 4-poles circuit breaker with a minimum contact gap of 3.0mm. (Only applicable for
S*C12*9E8/S*C16*9E8)
11. Ensure the correct polarity is maintained throughout all wiring. Otherwise, it will cause electrical shock or fire.
12.
After installation, check the water leakage condition in connection area during test run. If leakage occurs, it will cause damage to other
properties.
Installation work.
13. It may need two or more people to carry out the installation work. The weight of Indoor Unit / Outdoor Unit might cause injury if carried
by one person.
Содержание FHIF-WHS-120CE3
Страница 2: ......
Страница 9: ...R32 ATW Service Manual 7 1 2 2 Hydronic module FHIF WHS 120CE3 FHIF WHS 160CE3...
Страница 18: ...R32 ATW Service Manual 16 Pic 4 3 Domestic hot water mode operation range...
Страница 23: ...R32 ATW Service Manual 21 8 System diagram...
Страница 24: ...R32 ATW Service Manual 22 9 Wiring diagram 9 1 Outdoor unit 9 1 1 9 1 2 FHOF WHS 100CE3 FHOF WHS 160CE3 3F...
Страница 28: ...R32 ATW Service Manual 26 Main PCB 3 Hydronic module Main PCB...
Страница 29: ...R32 ATW Service Manual 27 Filter board...
Страница 34: ...R32 ATW Service Manual 32 Model FHOF WHS 160CE3 3F...
Страница 35: ...R32 ATW Service Manual 33 Single unit installation More than one unit installation Unit mm...
Страница 46: ...R32 ATW Service Manual 44 HEATING MODE COOLING MODE...
Страница 47: ...R32 ATW Service Manual 45 HEATING MODE WITHOUT COOLING MODE DHW MODE WITHOUT COOLING MODE...
Страница 48: ...R32 ATW Service Manual 46 HEATING MODE WITHOUT DHW MODE AND DHW TANK ONLY DHW MODE...
Страница 56: ...R32 ATW Service Manual 54 When the unit has error code alarm port has a 220V output...
Страница 59: ...R32 ATW Service Manual 57...