3.1.2.4

 

Under this mode, the corresponding protections are in effective (3- minute delayed start-up, over current, 
outdoor protection and evaporator low temperature protection.). Corresponding protection will act once any 
protection is in active. 

            Push “manual” pad once to end this mode and enter the remote control pending status. The buzzer will buzz for 

1 second and the indicator turn off. 

3.1.3 Manual Action 
3.1.3.1 Under this mode, the remote signal will be received and corresponding actions will be taken accordingly upon 

the receipt of the remote signal. 

3.1.3.2

 

On entering this mode, the buzzer will buzz for 0.5 second and the indicator on. 

3.1.3.3

 

The system will operate under the auto mode whose temperature is set to be 24°C and at the same time, the 
wind grille will swing automatically. 

3.1.3.4

 

Under this mode, corresponding protections are in effective. 

3.1.3.5

 

Push “ manual” pad to end this mode and switch over to manual cooling mode.       

 

3.2 Heating Mode

 

3.2.1 Four-way valve opens at once, while defrosting process closes. 
3.2.2 Condition for the compressor action: (Ts = set temperature, Ta = room temperature) 

 Condition 

Compressor 

Outdoor 

fan 

Ta

 > Ts+4 

Off Off 

Room temp. up 

Ta

 <Ts+4 

On On 

Ta

 < Ts+3 

On On 

Room temp. down 

Ta

 >Ts+3 

Off Off 

3.2.3 Indoor Fan Action 
3.2.3.1 Anytime remote switchover for fan speed among high/low/auto(anti-cold air function takes priority). 
3.2.3.2 Anti-cold air: 

Switchover between fan speed and fine tune can be set according to temperature of evaporator pipe. 

 Condition 

T= Indoor exchanger temp.   

Indoor fan speed 

T<25°C Off 

25°C <T<32°C 

Breeze 

Indoor exchanger temp. up 

T>32°C Setting 

fan 

speed 

T> 30°C 

Setting fan speed 

15°C <T<30°C 

Breeze 

Indoor exchanger temp. down 

T<15°C Off 

During anti-cold air period, if indoor fan is shut down, then pre-heating/defrosting lamp is on. Once indoor fan 
starts, pre-heating/defrosting lamp will be off. 
 

3.2.3.3 Auto fan of indoor fan under heating mode.   

 

Condition    (T =Indoor Temp.-Setting Temp.) 

Indoor fan speed 

T<3°C High 

Room  temp. up 

T>3°C Low 

 

T> 1°C 

Low   

Room  temp. down 

T<1°C High 

 

 

- 16 -

Содержание FSL-124HF

Страница 1: ...TECHNICAL SERVICE MANUAL DUCT SLIM TYPE AIR CONDITIONER FSL 124HF FSL 184HF FSL 244HF FI SM 040823...

Страница 2: ...Table 9 Part 6 Outlines and Dimension 12 Part 7 Electric Control Functions 15 Part 8 Wiring Diagram 24 Part 9 Installation 24 Part 10 Servicing and Maintenance 27 Part 11 Exploded view 29 NOTICE Spec...

Страница 3: ...Part 1 Product Features Quietest operation low noise Thin design space saving Easy to operate remote control 2...

Страница 4: ...Supplier TOSHIBA GUANG DONG Capacity Btu h 14600 14800 Input W 1400 1430 Rated current RLA A 6 5 Locked rotor Amp LRA A 7 5 Thermal protector UP3RE0591 T56 Capacitor uF 35 Compressor Refrigerant oil m...

Страница 5: ...Packing W H D mm 890 655 355 Outdoor unit Net Gross weight Kg 40 45 Refrigerant type R407C g 1330 Design pressure MPa 1 2 3 5 Liquid side Gas side mm inch 6 35 12 7 1 4 1 2 Max refrigerant pipe lengt...

Страница 6: ...OREA Capacity Btu h 20130 20267 29000 Input W 1980 2105 2760 Rated current RLA A 9 7 10 3 12 4 Locked rotor Amp LRA A 50 61 Thermal protector INTERNAL TYPE INTERNAL TYPE Capacitor uF 40 60 Compressor...

Страница 7: ...48 52 Dimension W H D mm 845X695X335 895X860X330 Packing W H D mm 965X847X395 972X987X406 Outdoor unit Net Gross weight kg 55 58 79 90 Refrigerant type g R407C 2050 R407C 2500 Design pressure MPa 1 2...

Страница 8: ...igh airflow FSL 124HF FSL 184HF Octave band center frequency Hz Sound pressure level dB 0dB 0 0002 bar Audibility limits of continuous white sound FSL 244HF Octave band center frequency Hz Sound press...

Страница 9: ...Part 4 Operation Range Ensure the operating temperature is in allowable range 8...

Страница 10: ...4 89 4 68 4 51 4 26 4 08 3 96 3 83 Sensitive capacity kW 3 91 3 74 3 61 3 40 3 27 3 17 3 06 32 C D 23 C W Input kW 1 13 1 29 1 45 1 61 1 77 1 93 2 09 Model FSL 124HF HEATING OUTDOOR TEMPERATURE Indoor...

Страница 11: ...6 10 5 85 5 67 5 49 Sensitive capacity kW 5 61 5 36 5 17 4 88 4 68 4 53 4 39 32 C D 23 C W Input kW 1 77 2 02 2 28 2 53 2 78 3 04 3 29 Model FSL 184HF HEATING OUTDOOR TEMPERATURE Indoor Conditions 24...

Страница 12: ...8 28 7 95 7 70 7 45 Sensitive capacity kW 7 62 7 29 7 02 6 62 6 36 6 16 5 96 32 C D 23 C W Input kW 2 50 2 85 3 21 3 57 3 92 4 28 4 63 Model FSL 244HF HEATING OUTDOOR TEMPERATURE Indoor Conditions 24...

Страница 13: ...Part 6 Outlines and Dimension 7 1 Indoor unit FSL 124HF FSL 184HF 12...

Страница 14: ...FSL 244HF 7 2 Outdoor unit FSO 124HF 13...

Страница 15: ...FSO 184HF 12 5 FSO 244HF A BODY DIMENSION B BODY DIMENSION C INSTALL BOLTS D INSTALL BOLTS E INSTALL BOLTS F INSTALL BOLTS G BASE FOOT H WATER RECEIVER 895 300 330 590 163 141 355 1013 14...

Страница 16: ...ion 3 1 1 The manual operation mode is controlled through manual pad in the wind in take grid including such two modes as manual action and manual cooling Push the manual pad for each switchover the o...

Страница 17: ...er to manual cooling mode 3 2 Heating Mode 3 2 1 Four way valve opens at once while defrosting process closes 3 2 2 Condition for the compressor action Ts set temperature Ta room temperature Condition...

Страница 18: ...es 3 3 1 3 3 Temperature of outdoor coil T3 is up to 20 C 3 3 1 4 Ending Action of Defrost 3 3 1 4 1 Outdoor fan and four way valve are open 3 3 1 4 2 Compressor keeps on continuously 3 3 1 4 3 Indoor...

Страница 19: ...3 6 4 Protective condition is actived 3 7 Fan Only Mode 3 7 1 Under this mode four way valve compressor and outdoor fan are shut down 3 7 2 High Low Auto fan can be switched over through manual contro...

Страница 20: ...shut down for protection c When there are 4 times compressor protection within one hour the A C will be shut down meanwhile the operation light and timer light will be turned on the defrosting light...

Страница 21: ...rent protection of the compressor occurs 4 times in 1h Lamps of operation timer defrosting only fan flashing simultaneously at 5Hz Whole unit is shut down It cannot recover unless power is cut off 2 p...

Страница 22: ...4 C N 1 C N 24 R T2 R T1 T4 XT1 C AP1 FAN 1 L 3 2 N 1 N XT1 KM 1 KM 1 4 XT2 FSO 124HF Outdoor unit 4 W AY VALVE BLU E TO I N D O O R U N I T XT1 W H I TE BLU E BLAC K R ED Y G BLU E R ED Y G Y G BLAC...

Страница 23: ...FSL 184HF Indoor unit FSO 184HF Outdoor unit 22...

Страница 24: ...FSL 244HF Indoor unit 3 1 N L 2 XT1 XS1 XS3 XT1 XT2 CAP1 FAN1 XP1 XP3 RT2 RT1 CN1 CN16 T4 FSO 244HF Outdoor unit XT3 VALVE R T3 XT1 XT2 XS1 XP1 KM 1 FAN C AP2 C O M P C AP1 23...

Страница 25: ...uit of the cool discharge Comply to the installation clearance recommended Don t put the indoor unit where there is direct sunlight on unit Make sure the location is suitable for piping and drainage F...

Страница 26: ...pipe immediately in 5 minutes If the nuts have been loosened for a long time dusts and other impurities may enter the pipe system and may cause malfunction later So please expel the air out of the pi...

Страница 27: ...age fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the outdoor and indoor units The gas side and liquid side stop values are both opened The air conditio...

Страница 28: ...Cause Solutions Power failure Wait for the comeback of power Power switch is open Switch on the power Fuse of power switch may have blown Replace the fuse Batteries remote of controller are exhausted...

Страница 29: ...ck whether the timer operation has come to an end when the OFF TIMER is indicated on the display The air conditioner operation stops since the set time elapsed The ON TIMER indicators go off after a l...

Страница 30: ...lector 1 25 4 Wire joint 1 9 Capacity 1 25 5 Relay 1 10 Capacitor box 1 26 E Parts box cover 1 11 Right fixing clamp for motor 1 27 Pipe supporting board 1 12 Left fixing clamp for motor 1 28 Pipe cla...

Страница 31: ...iring 1 7 Foam over holder for motor 1 25 Gas pipe valve 1 8 Cover 1 26 Liquid pipe valve 1 9 Fixing clamp for condenser 2 27 Separating board 1 10 Condenser 1 28 Compressor 1 11 Antivibration sponge...

Страница 32: ...board II 1 10 Capacitor box 1 28 Holder for remote controller 1 11 Axis 1 29 Remote controller 1 12 Bearing 1 30 E Parts box cover 1 13 Bearing seat 1 31 Pipe supporting board 1 14 Fan ass y 3 32 Pip...

Страница 33: ...egregator 1 9 Support board Left Side 1 26 Four way Valve 1 10 Rear Net 1 Four way Valve Solenoid 1 11 Support board Back side 1 27 High Pressure Valve 1 4 in 1 12 Handle 2 28 Capillary pipe Ass y 1 1...

Страница 34: ...33 33...

Отзывы: