2.

 

Refrigerant pipe connecting 

(1) Maximum pipe length 

Model 

Max. Length 

Max. Elevation 

FSL124-184-244HF 15m 

5m 

 
(2) Piping sizes 

Model Liquid(mm/inch) 

Gas(mm/inch) 

FSL-124HF 6.35(1/4) 

12.7(1/2) 

FSL-184HF. 6.35(1/4) 12.7(1/2) 

FSL-244HF 9.52(3/8) 

16.0(5/8) 

 
(3) Piping connection 

1). Measure the necessary length of the connecting pipe, and make it by the following way. 
a.

 

Connect the indoor unit at first, then the outdoor unit. 

Bend the tubing in proper way. Do not harm them. 
CAUTIONS 

Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds   
With hands before fasten the flare nuts.   
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes. 

Tubing size 

Torque 

6.35 1420~1720N.cm(144~176kgf.cm) 
9.52 3270~3990N.cm(333~407kgf.cm) 
12.7 4950~6030N.cm(504~616kgf.cm) 

16 6180~7540N.cm(630~770kgf.cm) 

b.

 

The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first 
loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have 
been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction 
later. So please expel the air out of the pipe with refrigerant before connection. 

c.

 

Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at 
the repair-points. 

2) Locate The Pipe 

a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall 
conduit and its cover. 
b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause 

water leakage by condensation. 

c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no 
damage to the tubing. 

3) Connect the pipes. 
4) Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with 

the outdoor unit in fluent flow. 

5) Be sure of no leakage by checking it with leak detector or soap water. 
6) Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it 

well with the tapes to prevent leakage. 

 

- 25 -

Содержание FSL-124HF

Страница 1: ...TECHNICAL SERVICE MANUAL DUCT SLIM TYPE AIR CONDITIONER FSL 124HF FSL 184HF FSL 244HF FI SM 040823...

Страница 2: ...Table 9 Part 6 Outlines and Dimension 12 Part 7 Electric Control Functions 15 Part 8 Wiring Diagram 24 Part 9 Installation 24 Part 10 Servicing and Maintenance 27 Part 11 Exploded view 29 NOTICE Spec...

Страница 3: ...Part 1 Product Features Quietest operation low noise Thin design space saving Easy to operate remote control 2...

Страница 4: ...Supplier TOSHIBA GUANG DONG Capacity Btu h 14600 14800 Input W 1400 1430 Rated current RLA A 6 5 Locked rotor Amp LRA A 7 5 Thermal protector UP3RE0591 T56 Capacitor uF 35 Compressor Refrigerant oil m...

Страница 5: ...Packing W H D mm 890 655 355 Outdoor unit Net Gross weight Kg 40 45 Refrigerant type R407C g 1330 Design pressure MPa 1 2 3 5 Liquid side Gas side mm inch 6 35 12 7 1 4 1 2 Max refrigerant pipe lengt...

Страница 6: ...OREA Capacity Btu h 20130 20267 29000 Input W 1980 2105 2760 Rated current RLA A 9 7 10 3 12 4 Locked rotor Amp LRA A 50 61 Thermal protector INTERNAL TYPE INTERNAL TYPE Capacitor uF 40 60 Compressor...

Страница 7: ...48 52 Dimension W H D mm 845X695X335 895X860X330 Packing W H D mm 965X847X395 972X987X406 Outdoor unit Net Gross weight kg 55 58 79 90 Refrigerant type g R407C 2050 R407C 2500 Design pressure MPa 1 2...

Страница 8: ...igh airflow FSL 124HF FSL 184HF Octave band center frequency Hz Sound pressure level dB 0dB 0 0002 bar Audibility limits of continuous white sound FSL 244HF Octave band center frequency Hz Sound press...

Страница 9: ...Part 4 Operation Range Ensure the operating temperature is in allowable range 8...

Страница 10: ...4 89 4 68 4 51 4 26 4 08 3 96 3 83 Sensitive capacity kW 3 91 3 74 3 61 3 40 3 27 3 17 3 06 32 C D 23 C W Input kW 1 13 1 29 1 45 1 61 1 77 1 93 2 09 Model FSL 124HF HEATING OUTDOOR TEMPERATURE Indoor...

Страница 11: ...6 10 5 85 5 67 5 49 Sensitive capacity kW 5 61 5 36 5 17 4 88 4 68 4 53 4 39 32 C D 23 C W Input kW 1 77 2 02 2 28 2 53 2 78 3 04 3 29 Model FSL 184HF HEATING OUTDOOR TEMPERATURE Indoor Conditions 24...

Страница 12: ...8 28 7 95 7 70 7 45 Sensitive capacity kW 7 62 7 29 7 02 6 62 6 36 6 16 5 96 32 C D 23 C W Input kW 2 50 2 85 3 21 3 57 3 92 4 28 4 63 Model FSL 244HF HEATING OUTDOOR TEMPERATURE Indoor Conditions 24...

Страница 13: ...Part 6 Outlines and Dimension 7 1 Indoor unit FSL 124HF FSL 184HF 12...

Страница 14: ...FSL 244HF 7 2 Outdoor unit FSO 124HF 13...

Страница 15: ...FSO 184HF 12 5 FSO 244HF A BODY DIMENSION B BODY DIMENSION C INSTALL BOLTS D INSTALL BOLTS E INSTALL BOLTS F INSTALL BOLTS G BASE FOOT H WATER RECEIVER 895 300 330 590 163 141 355 1013 14...

Страница 16: ...ion 3 1 1 The manual operation mode is controlled through manual pad in the wind in take grid including such two modes as manual action and manual cooling Push the manual pad for each switchover the o...

Страница 17: ...er to manual cooling mode 3 2 Heating Mode 3 2 1 Four way valve opens at once while defrosting process closes 3 2 2 Condition for the compressor action Ts set temperature Ta room temperature Condition...

Страница 18: ...es 3 3 1 3 3 Temperature of outdoor coil T3 is up to 20 C 3 3 1 4 Ending Action of Defrost 3 3 1 4 1 Outdoor fan and four way valve are open 3 3 1 4 2 Compressor keeps on continuously 3 3 1 4 3 Indoor...

Страница 19: ...3 6 4 Protective condition is actived 3 7 Fan Only Mode 3 7 1 Under this mode four way valve compressor and outdoor fan are shut down 3 7 2 High Low Auto fan can be switched over through manual contro...

Страница 20: ...shut down for protection c When there are 4 times compressor protection within one hour the A C will be shut down meanwhile the operation light and timer light will be turned on the defrosting light...

Страница 21: ...rent protection of the compressor occurs 4 times in 1h Lamps of operation timer defrosting only fan flashing simultaneously at 5Hz Whole unit is shut down It cannot recover unless power is cut off 2 p...

Страница 22: ...4 C N 1 C N 24 R T2 R T1 T4 XT1 C AP1 FAN 1 L 3 2 N 1 N XT1 KM 1 KM 1 4 XT2 FSO 124HF Outdoor unit 4 W AY VALVE BLU E TO I N D O O R U N I T XT1 W H I TE BLU E BLAC K R ED Y G BLU E R ED Y G Y G BLAC...

Страница 23: ...FSL 184HF Indoor unit FSO 184HF Outdoor unit 22...

Страница 24: ...FSL 244HF Indoor unit 3 1 N L 2 XT1 XS1 XS3 XT1 XT2 CAP1 FAN1 XP1 XP3 RT2 RT1 CN1 CN16 T4 FSO 244HF Outdoor unit XT3 VALVE R T3 XT1 XT2 XS1 XP1 KM 1 FAN C AP2 C O M P C AP1 23...

Страница 25: ...uit of the cool discharge Comply to the installation clearance recommended Don t put the indoor unit where there is direct sunlight on unit Make sure the location is suitable for piping and drainage F...

Страница 26: ...pipe immediately in 5 minutes If the nuts have been loosened for a long time dusts and other impurities may enter the pipe system and may cause malfunction later So please expel the air out of the pi...

Страница 27: ...age fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the outdoor and indoor units The gas side and liquid side stop values are both opened The air conditio...

Страница 28: ...Cause Solutions Power failure Wait for the comeback of power Power switch is open Switch on the power Fuse of power switch may have blown Replace the fuse Batteries remote of controller are exhausted...

Страница 29: ...ck whether the timer operation has come to an end when the OFF TIMER is indicated on the display The air conditioner operation stops since the set time elapsed The ON TIMER indicators go off after a l...

Страница 30: ...lector 1 25 4 Wire joint 1 9 Capacity 1 25 5 Relay 1 10 Capacitor box 1 26 E Parts box cover 1 11 Right fixing clamp for motor 1 27 Pipe supporting board 1 12 Left fixing clamp for motor 1 28 Pipe cla...

Страница 31: ...iring 1 7 Foam over holder for motor 1 25 Gas pipe valve 1 8 Cover 1 26 Liquid pipe valve 1 9 Fixing clamp for condenser 2 27 Separating board 1 10 Condenser 1 28 Compressor 1 11 Antivibration sponge...

Страница 32: ...board II 1 10 Capacitor box 1 28 Holder for remote controller 1 11 Axis 1 29 Remote controller 1 12 Bearing 1 30 E Parts box cover 1 13 Bearing seat 1 31 Pipe supporting board 1 14 Fan ass y 3 32 Pip...

Страница 33: ...egregator 1 9 Support board Left Side 1 26 Four way Valve 1 10 Rear Net 1 Four way Valve Solenoid 1 11 Support board Back side 1 27 High Pressure Valve 1 4 in 1 12 Handle 2 28 Capillary pipe Ass y 1 1...

Страница 34: ...33 33...

Отзывы: