2.
Refrigerant pipe connecting
(1) Maximum pipe length
Model
Max. Length
Max. Elevation
FSL124-184-244HF 15m
5m
(2) Piping sizes
Model Liquid(mm/inch)
Gas(mm/inch)
FSL-124HF 6.35(1/4)
12.7(1/2)
FSL-184HF. 6.35(1/4) 12.7(1/2)
FSL-244HF 9.52(3/8)
16.0(5/8)
(3) Piping connection
1). Measure the necessary length of the connecting pipe, and make it by the following way.
a.
Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
CAUTIONS
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Tubing size
Torque
6.35 1420~1720N.cm(144~176kgf.cm)
9.52 3270~3990N.cm(333~407kgf.cm)
12.7 4950~6030N.cm(504~616kgf.cm)
16 6180~7540N.cm(630~770kgf.cm)
b.
The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first
loosen the nuts at the part of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have
been loosened for a long time, dusts and other impurities may enter the pipe system and may cause malfunction
later. So please expel the air out of the pipe with refrigerant before connection.
c.
Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at
the repair-points.
2) Locate The Pipe
a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall
conduit and its cover.
b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause
water leakage by condensation.
c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no
damage to the tubing.
3) Connect the pipes.
4) Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with
the outdoor unit in fluent flow.
5) Be sure of no leakage by checking it with leak detector or soap water.
6) Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it
well with the tapes to prevent leakage.
- 25 -
Содержание FSL-124HF
Страница 1: ...TECHNICAL SERVICE MANUAL DUCT SLIM TYPE AIR CONDITIONER FSL 124HF FSL 184HF FSL 244HF FI SM 040823...
Страница 9: ...Part 4 Operation Range Ensure the operating temperature is in allowable range 8...
Страница 13: ...Part 6 Outlines and Dimension 7 1 Indoor unit FSL 124HF FSL 184HF 12...
Страница 14: ...FSL 244HF 7 2 Outdoor unit FSO 124HF 13...
Страница 23: ...FSL 184HF Indoor unit FSO 184HF Outdoor unit 22...
Страница 34: ...33 33...