Part 7. Electric Control Functions 

1. Performance Index

 

  No. 

Item 

Index 

1 Applicable 

Voltage 

Range 

165-253V~ 

2 A/C 

Frequency 

50Hz 

Working environment temperature 

-7°C- +45°C 

2. Main Parts Introduction 

 

2.1 Indoor Fan 

High speed and low speed.   
Breeze speed for anti-cold air. 

2.2 Outdoor Fan 

One speed.   

2.3 Buzzer

 

2.3.1.It will buzz when its driving port in the main chip outputs high level. 
2.3.2 It will buzz once when the main frame receives remote start-up signal. 
2.3.3It will buzz once for 1 second when receiving turn-off signal. 
2.3.4It will buzz for 0.5 second once receiving other signal. 

2.4 Indicator

 

2.4.1 There are 4 indicators: operating indicator, timer indicator, defrosting -pre-heating indicator ,water level warning 

indicator(without meaning at this type) 

2.4.2LED indicates errors when protection is in effective. 

2.5 Four-way Valve 

It is controlled by relays.   

 

3.1 Manual Operation 

3.1.1 The manual operation mode is controlled through “manual” pad in the wind in-take grid, including such two 

modes as manual action and manual cooling. Push the manual pad for each switchover, the order for which is 
shown below:   

 
     
   
                   

REMOTE CONTROL 

MANUAL ACTION 

MANUAL COOLING 

3.1.2 Manual Cooling 
3.1.2.1 Under this mode, no remote control signal will be received. 
3.1.2.2 The compressor is started up unconditionally and the rotating speed of indoor and outdoor fans is set to be in 

high and forced cooling operation. At the same time, the wind grille is forced to swing (irrelevant to temperature 
setting and environment temperature) and will be automatically switched over to manual mode 30 minutes later, 
under which manual mode will be in effective.   

3.1.2.3

 

Under this mode, the buzzer will buzz twice with each lasting 0.5 second at 0.5 interval. During the first 30 
minutes of unconditional forced cooling operation, the operation indicator will blink at 0.5Hz. In the process of 
switchover to manual action mode, the buzzer buzzes for 0.5 second and the indicator is illuminated. 

 

- 15 -

Содержание FSL-124HF

Страница 1: ...TECHNICAL SERVICE MANUAL DUCT SLIM TYPE AIR CONDITIONER FSL 124HF FSL 184HF FSL 244HF FI SM 040823...

Страница 2: ...Table 9 Part 6 Outlines and Dimension 12 Part 7 Electric Control Functions 15 Part 8 Wiring Diagram 24 Part 9 Installation 24 Part 10 Servicing and Maintenance 27 Part 11 Exploded view 29 NOTICE Spec...

Страница 3: ...Part 1 Product Features Quietest operation low noise Thin design space saving Easy to operate remote control 2...

Страница 4: ...Supplier TOSHIBA GUANG DONG Capacity Btu h 14600 14800 Input W 1400 1430 Rated current RLA A 6 5 Locked rotor Amp LRA A 7 5 Thermal protector UP3RE0591 T56 Capacitor uF 35 Compressor Refrigerant oil m...

Страница 5: ...Packing W H D mm 890 655 355 Outdoor unit Net Gross weight Kg 40 45 Refrigerant type R407C g 1330 Design pressure MPa 1 2 3 5 Liquid side Gas side mm inch 6 35 12 7 1 4 1 2 Max refrigerant pipe lengt...

Страница 6: ...OREA Capacity Btu h 20130 20267 29000 Input W 1980 2105 2760 Rated current RLA A 9 7 10 3 12 4 Locked rotor Amp LRA A 50 61 Thermal protector INTERNAL TYPE INTERNAL TYPE Capacitor uF 40 60 Compressor...

Страница 7: ...48 52 Dimension W H D mm 845X695X335 895X860X330 Packing W H D mm 965X847X395 972X987X406 Outdoor unit Net Gross weight kg 55 58 79 90 Refrigerant type g R407C 2050 R407C 2500 Design pressure MPa 1 2...

Страница 8: ...igh airflow FSL 124HF FSL 184HF Octave band center frequency Hz Sound pressure level dB 0dB 0 0002 bar Audibility limits of continuous white sound FSL 244HF Octave band center frequency Hz Sound press...

Страница 9: ...Part 4 Operation Range Ensure the operating temperature is in allowable range 8...

Страница 10: ...4 89 4 68 4 51 4 26 4 08 3 96 3 83 Sensitive capacity kW 3 91 3 74 3 61 3 40 3 27 3 17 3 06 32 C D 23 C W Input kW 1 13 1 29 1 45 1 61 1 77 1 93 2 09 Model FSL 124HF HEATING OUTDOOR TEMPERATURE Indoor...

Страница 11: ...6 10 5 85 5 67 5 49 Sensitive capacity kW 5 61 5 36 5 17 4 88 4 68 4 53 4 39 32 C D 23 C W Input kW 1 77 2 02 2 28 2 53 2 78 3 04 3 29 Model FSL 184HF HEATING OUTDOOR TEMPERATURE Indoor Conditions 24...

Страница 12: ...8 28 7 95 7 70 7 45 Sensitive capacity kW 7 62 7 29 7 02 6 62 6 36 6 16 5 96 32 C D 23 C W Input kW 2 50 2 85 3 21 3 57 3 92 4 28 4 63 Model FSL 244HF HEATING OUTDOOR TEMPERATURE Indoor Conditions 24...

Страница 13: ...Part 6 Outlines and Dimension 7 1 Indoor unit FSL 124HF FSL 184HF 12...

Страница 14: ...FSL 244HF 7 2 Outdoor unit FSO 124HF 13...

Страница 15: ...FSO 184HF 12 5 FSO 244HF A BODY DIMENSION B BODY DIMENSION C INSTALL BOLTS D INSTALL BOLTS E INSTALL BOLTS F INSTALL BOLTS G BASE FOOT H WATER RECEIVER 895 300 330 590 163 141 355 1013 14...

Страница 16: ...ion 3 1 1 The manual operation mode is controlled through manual pad in the wind in take grid including such two modes as manual action and manual cooling Push the manual pad for each switchover the o...

Страница 17: ...er to manual cooling mode 3 2 Heating Mode 3 2 1 Four way valve opens at once while defrosting process closes 3 2 2 Condition for the compressor action Ts set temperature Ta room temperature Condition...

Страница 18: ...es 3 3 1 3 3 Temperature of outdoor coil T3 is up to 20 C 3 3 1 4 Ending Action of Defrost 3 3 1 4 1 Outdoor fan and four way valve are open 3 3 1 4 2 Compressor keeps on continuously 3 3 1 4 3 Indoor...

Страница 19: ...3 6 4 Protective condition is actived 3 7 Fan Only Mode 3 7 1 Under this mode four way valve compressor and outdoor fan are shut down 3 7 2 High Low Auto fan can be switched over through manual contro...

Страница 20: ...shut down for protection c When there are 4 times compressor protection within one hour the A C will be shut down meanwhile the operation light and timer light will be turned on the defrosting light...

Страница 21: ...rent protection of the compressor occurs 4 times in 1h Lamps of operation timer defrosting only fan flashing simultaneously at 5Hz Whole unit is shut down It cannot recover unless power is cut off 2 p...

Страница 22: ...4 C N 1 C N 24 R T2 R T1 T4 XT1 C AP1 FAN 1 L 3 2 N 1 N XT1 KM 1 KM 1 4 XT2 FSO 124HF Outdoor unit 4 W AY VALVE BLU E TO I N D O O R U N I T XT1 W H I TE BLU E BLAC K R ED Y G BLU E R ED Y G Y G BLAC...

Страница 23: ...FSL 184HF Indoor unit FSO 184HF Outdoor unit 22...

Страница 24: ...FSL 244HF Indoor unit 3 1 N L 2 XT1 XS1 XS3 XT1 XT2 CAP1 FAN1 XP1 XP3 RT2 RT1 CN1 CN16 T4 FSO 244HF Outdoor unit XT3 VALVE R T3 XT1 XT2 XS1 XP1 KM 1 FAN C AP2 C O M P C AP1 23...

Страница 25: ...uit of the cool discharge Comply to the installation clearance recommended Don t put the indoor unit where there is direct sunlight on unit Make sure the location is suitable for piping and drainage F...

Страница 26: ...pipe immediately in 5 minutes If the nuts have been loosened for a long time dusts and other impurities may enter the pipe system and may cause malfunction later So please expel the air out of the pi...

Страница 27: ...age fits the rated voltage of the air conditioner There is no obstacle at the outlet and inlet of the outdoor and indoor units The gas side and liquid side stop values are both opened The air conditio...

Страница 28: ...Cause Solutions Power failure Wait for the comeback of power Power switch is open Switch on the power Fuse of power switch may have blown Replace the fuse Batteries remote of controller are exhausted...

Страница 29: ...ck whether the timer operation has come to an end when the OFF TIMER is indicated on the display The air conditioner operation stops since the set time elapsed The ON TIMER indicators go off after a l...

Страница 30: ...lector 1 25 4 Wire joint 1 9 Capacity 1 25 5 Relay 1 10 Capacitor box 1 26 E Parts box cover 1 11 Right fixing clamp for motor 1 27 Pipe supporting board 1 12 Left fixing clamp for motor 1 28 Pipe cla...

Страница 31: ...iring 1 7 Foam over holder for motor 1 25 Gas pipe valve 1 8 Cover 1 26 Liquid pipe valve 1 9 Fixing clamp for condenser 2 27 Separating board 1 10 Condenser 1 28 Compressor 1 11 Antivibration sponge...

Страница 32: ...board II 1 10 Capacitor box 1 28 Holder for remote controller 1 11 Axis 1 29 Remote controller 1 12 Bearing 1 30 E Parts box cover 1 13 Bearing seat 1 31 Pipe supporting board 1 14 Fan ass y 3 32 Pip...

Страница 33: ...egregator 1 9 Support board Left Side 1 26 Four way Valve 1 10 Rear Net 1 Four way Valve Solenoid 1 11 Support board Back side 1 27 High Pressure Valve 1 4 in 1 12 Handle 2 28 Capillary pipe Ass y 1 1...

Страница 34: ...33 33...

Отзывы: