2.2.1 Measuring lines that need to be connected
The following points need to be observed when connecting the pressure line:
• To ensure there is no influence on the measured values, severe bends and
coils in the wire should be avoided.
• To prevent deposits, there should be a continuous incline or drop of at least
8%.
• When measuring steam pressure, a water bag-forming loop must be
provided due to the temperature (see accessories).
Round shape
U-shape
G½
ca. 180
Ø20
56
155
ca. 200
G½
G½
ca. 275
ca. 130
Ø20
Ø56
G½
SW27
Manometer connection
Connection spigot
according to DIN EN 837-1
Illustration 7:
Siphon MZ1###
• The transmitter must be positioned below the measuring point for liquid
measurements. Vent the pressure line before commissioning.
• The transmitter must be positioned above the measuring point for gas
measurements.
2.2.2 Pressure surge absorption
Pulsating pressure on the system side can lead to functional problems. We re-
commend installing a damping element in the pressure connection lines as a
protective measure.
a) Capillary throttle
Manometer connection
SW27
SW27
Connection spigot
according to DIN EN 837-1