background image

3 | Commissioning

FISCHER Mess- und Regltechnik GmbH

20 / 32

BA_EN_MS13

3.3.6 Menu Level Display

The Display menu level is a variable menu whose appearance depends on the
value of the colour parameter. In addition to the various colours for the back-
ground lighting, there are also two auto-functions with colour switching avail-
able.

Parameter name

Description

Value range

Colour

Colour

Off, red, green, yellow,
blue, pink, turquoise,
white,

Auto1: Red-green
Auto2: Red-yellow-
green

Lighting

Lighting time

0 s, 10 … 600 s

Contrast

Contrast

15 … 45

Bar chart

Barchart display

yes, no

The mots important parameter is 

Colour

. A fixed colour can be defined for the

background colour here. There are also two auto-functions with colour switching
available. Alternatively, the background illumination can be permanently deac-
tivated.
If permanent lighting is not required, the parameter 

Lighting time

 can be used

to define when the lighting should be switched off after the last time a button is
pressed. In addition to permanent lighting (0 s), automatic shut-down after 10…
600 s is also possible. The set time is only valid if the parameter 

Colour

 is not

set to "off".
Amongst other things, the legibility of the display depends on the temperature
and the reading angle. To ensure optimised legibility, the display can be adjus-
ted using the parameter 

Contrast

. When the contrast is changed, it is possible

that the display appears empty or almost completely black. In this case, the
contrast must be turned up or down.
Via the parameter 

Bar chart

, the display can be switched between a display

where the measured value is either shown in large digits or the display shows
small digits and an additional barchart.

Auto1: Colour-change red to green

In the mode with the automatic colour switchover, it is possible to enter the re-
quired switch thresholds "red-green switchover", "green-red switchover".
The switching thresholds can be moved within the measuring range. The series
of switch points cannot be altered.

Parameter name

Description

Value range

Red-Gr. switch.

Red-green switching

MRS - 50% …
MRE + 50%

Gr-Red switch.

Green-red switching

Hysteresis

Hysteresis

0.1 … 10.0 %

Delay

Delay

0 … 1800 s

Colour

Colour

Off, red, green, yel-
low, blue, pink, tur-
quoise, white,

Auto1: Red-green
Auto2: Red-yellow-
green

Lighting

Lighting time

0 s, 10 … 600 s

Contrast

Contrast

15 … 45

Bar chart

Barchart display

yes, no

Содержание MS13

Страница 1: ...Operating manual MS13 Digital pressure transmitter switch with colour change display 09005885 BA_EN_MS13 Rev ST4 A 10 16 09005885...

Страница 2: ...sing electronic sys tems or any other form print photocopy microfilm or another process without the written consent of the company Fischer Mess und Regeltechnik GmbH Bad Salzuflen Reproduction for int...

Страница 3: ...mmissioning 12 3 1 General 12 3 2 Control elements 12 3 2 1 LC display 12 3 2 2 Keyboard 13 3 3 Menu levels 14 3 3 1 Menu Level Switch points 14 3 3 2 Menu Level Input 15 3 3 3 Menu Level Measuring 16...

Страница 4: ...lication areas Technical facility equipment TGA Process engineering Process technology Environmental technology 1 3 Intended use The MS13 is a pressure transmitter switch for measuring relative pressu...

Страница 5: ...6 7 Code U Process connection Illustration 1 Product Overview 1 Colour change display 2 Bayonet ring housing 3 Keyboard 4 Process connection 5 Blowout plug 6 M12 plug 1 7 M12 plug 2 Process connection...

Страница 6: ...of the information that is stated The data shown is purely fictive but does correspond to the actual conditions For more information please see the order code at the end of these instructions MESS UN...

Страница 7: ...nder pressure The pressure deforms the measuring mem brane causing a change in resistance on the attached measuring bridge This change is evaluated by the device s electronics and transformed into the...

Страница 8: ...llation however any installation posi tion is possible To guarantee safe working conditions during installation and maintenance suit able stop valves must be fitted in the system see accessories By me...

Страница 9: ...pe G ca 180 20 56 155 ca 200 G G ca 275 ca 130 20 56 G SW27 Manometer connection Connection spigot according to DIN EN 837 1 Illustration 7 Siphon MZ1 The transmitter must be positioned below the meas...

Страница 10: ...b Settable damping reactor In operating mode the damping throttle must be set so that the output signal follows the pressure changes with a delay G G 20 66 19 SW27 Setting screw Connection spigot acco...

Страница 11: ...not connect the connector if strained 3 Leiterschaltung Input Output AC DC Sensor Signal Ub Ub Sig Sig Ub Ub p 1 3 2 4 Connector 1 Supply and output signal Illustration 10 M12 connector 5 pin Item Des...

Страница 12: ...the pressure connections do not leak before commissioning 3 2 Control elements 3 2 1 LC display 1 3 4 2 Illustration 12 LC display 1 Measurement display 4 6 digits 2 Bar chart display 3 Status display...

Страница 13: ...e value is saved with the button To leave a menu level or the entire menu select the parameter Quit and press Example Switch on point set switchpoint 1 In normal mode press the button to enter the men...

Страница 14: ...ystemyou can change to the respective na tional language using the language parameter You can see which languages are supported there 3 3 1 Menu Level Switch points Parameter name Description Value ra...

Страница 15: ...hysteresis function If SP1 On SP1 Off the output switches on if the measured value exceeds SP1 On and off if the measured value undercuts the same value SP1 Off If SP1 On SP1 Off the output switches o...

Страница 16: ...lue x 2x x 2x Zero point window Illustration 16 Zero point window It makes sense to set the Offset zero point displacement if without differential pressure remove measuring line the display shows a va...

Страница 17: ...arameter Limit allows the display output and switching points to be lim ited to the range between Start of measuring range and End of measuring range This makes sense when content is measured to avoid...

Страница 18: ...Value range Function Function Value square rooted MB decimal pl Measuring range decimal places 1234 123 4 12 34 1 234 12345 123456 MB start Measuring range start 9999 9999 MB end Measuring range end 9...

Страница 19: ...ints are used in the table A table is made up of at least 3 max 30 support points NOTICE Number of value pairs If the number of value pairs is changed the table is initialised again and the ex isting...

Страница 20: ...e set time is only valid if the parameter Colour is not set to off Amongst other things the legibility of the display depends on the temperature and the reading angle To ensure optimised legibility th...

Страница 21: ...alid if the parameter Colour is not set to off The lighting can be switched on permanently with the value 0s The legibility of the display can be adjusted using the parameter Contrast When the contras...

Страница 22: ...tch Colour change yellow to red ME MB end Measuring range end In this menu the same parameters are used as those described in the previous sections NOTICE Unused range If a range is not to be used the...

Страница 23: ...y The operating time is shown in days d and hours h A Password can be used to protect the menu against unauthorised access The password is a figure from 1 to 999 The input 0 means that no password is...

Страница 24: ...5 FS 1 0 FS 0 10 bar 40 bar 70 bar 0 5 FS 1 0 FS 0 16 bar 40 bar 70 bar 0 5 FS 1 0 FS 0 25 bar 100 bar 150 bar 1 0 FS 0 40 bar 100 bar 150 bar 1 0 FS 0 60 bar 200 bar 250 bar 1 0 FS Vacuum and measur...

Страница 25: ...linearity and hysteresis 4 5 Auxiliary energy Rated Voltage 24 V AC DC Admissible operating voltage Ub 12 32 V DC Ub 16 5 32 V AC Electrical connection 5 pin M12 circular plug connector 4 6 Applicatio...

Страница 26: ...Output signal User definable within the basic measuring range 1 Zero point stabilising 0 of the basic measuring range 2 Zero point correction off set of the basic measuring range 3 Implementation of c...

Страница 27: ...S1 13 20 7 5 3 2 6 5 2 17 5 9 5 18 NPT 7 16 UNF G G G Illustration 23 Process connection Port Material G B Connection shanks with external thread 1 4404 G B Connection shanks with external thread 1 44...

Страница 28: ...1 PSI 09 0 25 bar 0 2500 kPa 0 362 6 PSI 10 0 40 bar 0 4000 kPa 0 580 1 PSI 11 0 60 bar 0 6000 kPa 0 870 2 PSI 31 1 0 bar 100 0 kPa 14 50 0 PSI 32 1 0 6 bar 100 60 kPa 14 50 8 702 PSI 33 1 1 5 bar 100...

Страница 29: ...em Design V FKM Fluororubber Viton 5 1 Accessories Order no Designation No of Poles Length 06401993 Connection cable for switching outputs with M12 connector 4 pin 2 m 06401994 Connection cable for sw...

Страница 30: ...6 Attachments FISCHER Mess und Regltechnik GmbH 30 32 BA_EN_MS13 6 Attachments Illustration 24 CE_DE_MS13...

Страница 31: ...FISCHER Mess und Regltechnik GmbH Attachments 6 BA_EN_MS13 31 32...

Страница 32: ...6 Attachments FISCHER Mess und Regltechnik GmbH 32 32 BA_EN_MS13...

Отзывы: