Installation and assembly | 3
BA_EN_ME11
9/24
3.2.1 Measuring lines that need to be connected
The following points need to be observed when connecting the pressure line:
• To ensure there is no influence on the measured values, severe bends and
coils in the wire should be avoided.
• To prevent deposits, there should be a continuous incline or drop of at least
8%.
• When measuring steam pressure, a water bag-forming loop must be
provided due to the temperature (see accessories).
Round shape
U-shape
G½
ca. 180
Ø20
56
155
ca. 200
G½
G½
ca. 275
ca. 130
Ø20
Ø56
G½
AF27
Manometer connection
Connection spigot
according to
DIN EN 837-1
Fig. 6:
Siphon MZ1###
• The transmitter must be positioned below the measuring point for liquid
measurements. Vent the pressure line before commissioning.
• The transmitter must be positioned above the measuring point for gas
measurements.
3.2.2 Pressure surge absorption
Pulsating pressure on the system side can lead to functional problems. We re-
commend installing a damping element in the pressure connection lines as a
protective measure.
a) Capillary throttle
Manometer connection
SW27
AF27
Connection spigot
according to DIN EN 837-1
305
110
G½
G½
Ø88
Ø4
Fig. 7:
Capillary throttle MZ400#
Содержание ME11 Series
Страница 1: ...Operating manual ME11 Pressure Transmitter 09005184 BA_EN_ME11 Rev ST4 B 04 22 09005184...
Страница 21: ...FISCHER Mess und Regeltechnik GMBH Attachments 7 BA_EN_ME11 21 24 7 Attachments Fig 16 CE_EN_ME11...
Страница 22: ...7 Attachments FISCHER Mess und Regeltechnik GMBH 22 24 BA_EN_ME11 Fig 17 UKCA_EN_ME11...
Страница 23: ...FISCHER Mess und Regeltechnik GMBH BA_EN_ME11 23 24 Notes...