valve on the system (see accessories section). This 
means that 

 

the device can be depressurized or taken out of 
operation 

 

the device can be disconnected from the power 
supply  within  the  applicable  system  for  repairs 
or inspections. 

• 

a  function  test  of  the  device  can  be  performed 
on-site. 

4.1 

Process connection 

• 

By authorized and qualified specialized person-
nel only. 

• 

Only  for  the  designated  mechanical  process 
connection  (for  the  model,  see  the  order  code 
on the device type plate) 

• 

The  pipes  need  to  be  depressurized  when  the 
device is being connected. 

• 

Appropriate  steps  must  be  taken  to  protect  the 
device from pressure surges. 

• 

Check the suitability of the device for the media 
to be measured. 

• 

Maximum pressures must be observed. 

• 

Check  that  the  pressure  connections  do  not 
leak before commissioning. 

4.1.1 

Pressure sensing lines 

Remark 

Commissioning  and  repeat  tests  can  be 
carried  out  more  efficiently  by  using  a 
suitable shut-off device. 

The  pressure  connections  are  marked  with (+)  and 
(-)  symbols  on  the  device.  For  differential  pressure 
measurements, the higher pressure is connected to 
the (+) side and the lower pressure to the (-) side of 
the device. When measuring the pressure, only the 
(+) connection is used; the (-) connection is used to 
measure under-pressure. 

The pressure sensing lines need to be kept as short 
as  possible  and  installed  without  sharp  bends  to 
avoid interfering delay times. 

The  pressure  sensing  lines  must  be  installed  on  a 
gradient so that no air pockets e.g. for liquid meas-
urements  or  water  pockets  e.g.  for  gas  measure-
ments  can  be  created.  If  the  required  inclination  is 
not reached, water or air filters must be installed at 
suitable places. 

If  liquid  measuring  media  are  used  the  pressure 
connection  lines  must  be  deaerated,  as  liquid  col-
umns  of  different  heights  in  the  pipes  can  cause 
measuring  errors.  The  instrument  must  be  protect-
ed against frost if water is used as a medium. 

4.1.2   Pressure surge absorption 

Pulsating  pressure  on  the  system  side  can  lead  to 
wear  and  functional  problems.  To  safeguard  this, 
we recommend installing absorption elements in the 
pressure pipe line. 

Fluid media 

 

 

In  the  operational  status,  the  reactor  pins  need  to 
be set so that the measurement display follows the 
pressure changes with a delay. 

Gaseous media 

 

4.2 

Electrical connections 

• 

By authorized and qualified specialized person-
nel only. 

Settable reactor pins below the clos-
ing cap 

G¼ 

Capillary throttle coil MZ 401 

Содержание DS 11

Страница 1: ...ar with the in stallation commissioning and operation of this product Specialized personnel are persons who can assess the work they have been assigned and recognize potential dangers by virtue of their specialized train ing their skills and experience and their knowledge of the pertinent standards 1 3 Risks due to Non Observance of Safe ty Instructions Non observance of these safety instructions ...

Страница 2: ...toring filters and pumps Pressure chamber and measuring diaphragms are available in various materials This allows the devices to be adapted to the various requirements 3 Product and functional description 3 1 Function diagram Item Description 1 Pressure chamber 2 Motion train 3 Tappet 4 Micro switch 5 Switch point setting 6 Measuring diaphragm 7 Measuring springs 3 2 Design and mode of operation A...

Страница 3: ...r pressure to the side of the device When measuring the pressure only the connection is used the connection is used to measure under pressure The pressure sensing lines need to be kept as short as possible and installed without sharp bends to avoid interfering delay times The pressure sensing lines must be installed on a gradient so that no air pockets e g for liquid meas urements or water pockets...

Страница 4: ... Set the measurement value pointer to the zero point scale using the zero point correction screw Re mount the hood 5 3 Switch point setting Remove the plug in the hood The required switch points can be set guide value scales according to the markings by us ing a screwdriver The achievable setting accu racy is 5 1 Replace the plug after completing the settings 5 4 Function test Remove both plugs in...

Страница 5: ...tected against impacts It should be transported in the original packaging or a suitable transport container 8 Service All defective or faulty devices should be sent direct ly to our repair department Please coordinate all shipments with our sales department Warning Process media residues in and on dismantled devices can be a hazard to people animals and the environment Take adequate preventive mea...

Страница 6: ...measuring range Switch hysteresis approx 2 5 of the upper range value Load data contact AC DC Umax 250V 30V Imax 5A 0 4A Pmax 250 VA 10 W Ports Process connection Inner thread G 1 4 Connecting shank G DIN EN 837 Cutting ring connections for 6 8 10 mm brass steel galvanized or stainless steel electr connection Fixed wire numbered cables Cable connection socket 7 pole plug connection Materials Press...

Страница 7: ... Process connection variants M20x1 5 Cable screw connection Cable connection socket or 7 pin plug connection SW19 Connection G inner thread Connection spigot G according to DIN EN 837 DZ 13 14 Four spindle equalization and shut off valve Mounting the control panel opened opened Measuring device Venting Function diagram DZ 13 14 Venting n a for DZ13 Cutting ring screw connection Control panel cut o...

Страница 8: ...read 1 4 18 NPT EXT Chrome Nickel Steel 1 4 Cutting ring screw connection made of steel for 6 mm pipe 2 0 Cutting ring screw connection made of steel for 8 mm pipe 2 1 Cutting ring screw connection made of steel for 10 mm pipe 2 2 Cutting ring screw connection made of 1 4571 for 6 mm pipe 2 4 Cutting ring screw connection made of 1 4571 for 8 mm pipe 2 5 Cutting ring screw connection made of 1 457...

Страница 9: ...d or taken out of operation for repairs or tests to disconnect differential pressure devices within the affected systems from the mains supply The shutoff devices can therefore also be used for function tests on site In contrast to DZ13 the DZ14 also has a venting valve to vent the conected pipe system The shutoff and venting valves are designed for the rated pressure level PN40 The housing can be...

Страница 10: ...10 16 Page 14 Manufacturer s Declarations and Certificates 14 1 EC Declaration of conformity ...

Страница 11: ...11 16 Page 14 2 Certificate functional security SIL2 ...

Страница 12: ...12 16 Page ...

Страница 13: ...13 16 Page 14 3 GL approval ...

Страница 14: ...14 16 Page ...

Страница 15: ...15 16 Page ...

Страница 16: ...ithout notice Changements techniques sous réserve Fischer Mess und Regeltechnik GmbH Bielefelder Str 37a D 32107 Bad Salzuflen Tel 49 5222 9740 Fax 49 5222 7170 eMail info fischermesstechnik de www fischermesstechnik de 14 4 EAC Declaration of conformity ...

Отзывы: