The table entries consist of 1 to 28 pairs of values. Valu-
es

I02

  through 

I29

  (or 

u02

  through 

u29

)  specify  the

amplitude  of  the  out  the  signal  output,  and  the  values

P02

 through 

P29

The table is accepted as correct if each output value is
larger than its preceding value. Pressure values can be
steadily  increasing  or  steadily  decreasing.  However,  a
transition from falling to rising pressure values is not per-
mitted;  nor  are  pressure  values  allowed  to  turn  back
along the same curve.

5.3.8. Limit Setting

The  two limit switching  outputs 

  (relay contacts or

solid-state switches) are each configured by four set-up
parameters:

Switching  output  1  is  configured  by  parameters 

R1A,

R1E, R1D

 and 

R1F

.

Switching  output  2  is  configured  by  parameters 

R2A,

R2E, R2D

 and 

R2F

.

The turn-on and turn-off points of switching output 1 are
defined  respectively  by  parameters 

R1A

  and 

R1E

.  The

values for these are set in the currently valid unit of me-
asurement (indicated by the lighted symbol to the right of
the digital display).

The two parameters 

R1A

 and 

R1E

 together determine the

logic of switching output 1:

If

R1A

 is smaller than 

R1E

, the output turns on when the

measured  value  exceeds 

R1E

.  It  turns  off  again  only

when  the  measured  value  falls  below 

R1A

  (hysteresis

function).

If

R1A

 and 

R1E

 have the same value, there is no hystere-

sis:  the  switching  output  turns  on  when  the  measured
value exceeds 

R1A

 / 

R1E

, and turns off again when the

measured value falls below 

R1A

 / 

R1E

.

If

R1A

 is larger than 

R1E

, the switching output turns on

when  the  measured  value  falls  between 

R1A

  and 

R1E

:

i.e.,  when 

R1E

  <  measured  value  < 

R1A

  (window  limit

function).

Both parameters can be independently adjusted over the
full measuring range.

If  the  unit  of  measurement  is  changed,  the  switching
points are changed accordingly. In this event, rounding
error can cause a deviation in the least significant (right-
most) digit.

The  value  of  the  set-up parameter 

R1D

  determines the

delay  time  for  switching  output  1,  after  the  measured
value reaches the switching point. The delay value can
be  selected in  the range 0.0  to  100.0  secs. This  value
applies equally to turn on and turn off.

The set-up parameter 

R1F

 determines the action of the

switching output. If 

R1F

 = 1, the switching output acts as

normally open (NO) contacts. If 

R1F

 = 2, it acts as nor-

mally closed (NC) contacts.

5.3.9. Password

The last set-up parameter allows a password to be ente-
red. A password value of 001 to 999 can be selected. A
value of 000 disables the password function.

If  a  password  was  set  previously  the  digital  display
indicates

PAS

 after 

Esc

 is displayed and 

û

 is pressed.

The password is then entered, by pressing 

û

 and then

þ

,

ÿ

. Only then will the set-up menu options be acces-

sible.  If  an  incorrect  password  is  entered,  the  display
jumps back to beginning of the menu (i.e., 

Esc

).

New Functions! (as of April 2008)

5.3.10.

 D0

– Display options

This parameter allows smoothing the displayed values in
cases  where  they  are  frequently  deviating.  The  filter
function is similar to the 

dAM

 function, but acts only upon

the display, having no impact on the output signal. Addi-
tionally the display can be turned off partially (

D0

 = -1,

only  the  setpoint  LEDs  are  driven)  or  completely
(

D0

 = -2).

5.3.11.

 res

– Reset to default values

This function will reset all parameters to default when ac-
tivated. Default values can be defined only by using the
PC interface.

5.3.12.

MAF, MEF, dPF 

– Free Unit

If the device is configured to have a “free“ third unit (sym-
bol:

)  then  the  display  can  be  scaled  as  desired  by

using these three parameters.

The measuring range as defined by parameters

MA

and

ME

is rescaled to 

MAF

 and 

MEF

. If the table function ( 

F

)

is  enabled,  table  values  will  be  taken into  account too.
The

dPF

 value controls the position of the decimal point.

Contact: EK Engineering (India)
Web: www.ekeindia.com
Email: [email protected]

All manuals and user guides at all-guides.com

all-guides.com

Содержание DE45 series

Страница 1: ...d inspection of this product must have the qualifications training and experience necessary to carry out such work on this type of equipment Qualified personnel are people who are able to ju dge deleg...

Страница 2: ...applies to the use of unautho rized spare parts for repair maintenance of the product Any modifications to this product if and as necessary should be done only by Fischer Mess und Regeltechnik GmbH 1...

Страница 3: ...ing system must meet specifications for zone 2 class 3 Electrical connections must comply with relevant international and local regulations and norms re lating to electrical and instrumentation instal...

Страница 4: ...lighted symbols to the right of the digital dis play To change the unit of measurement first press then search for parameter EIN using Next press again and select another unit of measurement using or...

Страница 5: ...ut signal value set as parameter oEr However it should be understood that not all instrument fault and er ror conditions can be detected and signaled by the self diagnostic functions of the instrument...

Страница 6: ...ast significant right most digit The value of the set up parameter R1D determines the delay time for switching output 1 after the measured value reaches the switching point The delay value can be sele...

Страница 7: ...e measured variable corresponding with the minimum value of the output signal 0 V 0 mA or 4 mA depending on the instrument version ME Measuring range end point The value of the measured variable corre...

Страница 8: ...the instruments Inspection and test schedules depend on operating and site conditions The operating manuals of other equip ment to which the transmitter is connected must be read thoroughly to ensure...

Страница 9: ...20 70 C IP 65 acc to DIN EN 60529 Electrical Data Nominal supply voltage Operating supply voltage Output signal 24 V DC AC 12 32 V DC AC 0 20 mA 4 20 mA 0 10 V DC 3 wire Output signal load For output...

Страница 10: ...h 1 2 activation point de activation point response time delay 0 0 100 0 secs logic N O or N C Measurement unit selection mbar Pa free unit start value end value and decimal place for free unit Zero s...

Страница 11: ...ge output 0 10 V DC linear 3 wire C Current output 4 20 mA linear 3 wire P Supply Voltage 24 V DC AC nominal 12 32 V DC AC K Display Switching output 3 digit LED 2 potential free semiconductor switch...

Страница 12: ...12 14 Declaration of Conformity Contact EK Engineering India Web www ekeindia com Email india eke gmail com All manuals and user guides at all guides com...

Отзывы: