zero. Only when the actual pressure is outside this range
will the display indicate a non-zero value. The actual and
displayed  pressures will agree starting from double  the
value of the 

NP

 setting (in the given example: 0.16 bar or

16 kPa).

5.3.4. Output Signal Setting

The  transmitter  output  signal  depends  primarily  on  the
measured pressure. However, this signal can be adapted
to  meet  users'  application  requirements  precisely.  The
basic  pressure  range  (as  marked  on  the  product  iden-
tification label) and the type of output signal (voltage or
current) always remain unchanged for a  particular  inst-
rument unit. 

The  set-up  parameters 

MA

  (measuring  range  starting

point)  and 

ME

  (measuring  range  end point)  specify  the

pressure values between which the measurements are
expected  to  be.  Both  values  can  selected  anywhere
within  the  specified  measuring  range  of  the  instrument
(e.g.,  400 kPa).  This  user-programmed  pressure range
will correspond to the output signal (current or voltage)
range,  which  will  be  as  specified  on  the  product  iden-
tification plate: i.e., 0 - 10V or 4 - 20 mA.

If

MA

 is lower than 

ME

, the signal is said to have a positive

slope:  i.e.,  the output  signal  increases  as  the pressure
increases. If 

ME

 is lower than 

MA

, the output signal has a

negative  slope: i.e., the output  signal decreases as the
pressure increases. 

The difference between the values of 

MA

 and 

ME

 must be

at least 25% of the specified measuring range of the ins-
trument  (100 kPa for 400 kPa instrument example men-
tioned  above). The  software  does  not  permit a  smaller
pressure span to be entered (the instrument will not allow
storing of, nor exit from an invalid span).

Note: If you change 

MA

 and/or 

ME

 the

look-up table (s .5.3.6., 5.3.7.) that exi-
sted up to that instant is deleted! 

5.3.5. Output Signal Limiting (Namur)

The three set-up parameters 

oG1

,

oG2

 and 

oEr

 specify

the limits of the signal output current or voltage that are
not to be exceeded, irrespective of the actual pressure.
These limit values have higher priority than the 

MA

 and

ME

 pressure span settings.

These settings serve mainly to prevent control systems
from  interpreting  brief  pressure  excursions  outside  the
measuring range as error / fault events. 

oG1

 sets the out-

put  signal  minimum  value,  and  is  useful  only  for  a
4 - 0 mA  current  signal,  because  sometimes  a  value
below 3.8 mA is defined as a sensor fault condition. 

oG2

sets the upper signal limit and is valid for either current or
voltage signal (e.g., voltage signal output can be limited
at 10.2 V).

An  instrument  fault  condition  can  be  transmitted  as  an
output  signal value  set  as  parameter 

oEr

.  However,  it

should be understood that not all instrument fault and er-
ror conditions can be detected and signaled by the self-
diagnostic functions of the instrument.

5.3.6. Signal Conversion and Transfer Functions

In certain cases other process variables are derived from
primary pressure measurement. Examples are flow rate
derived from differential pressure across an orifice plate,
and  liquid  level  derived  from  hydrostatic  pressure  of
liquid measured at the bottom of the tank. Such deriva-
tions often involve non-linear transfer functions, while it is
necessary for the output signal to be linearly proportional
to the derived variable (e.g. liquid volume in a tank in m

3

,

or flow rate in cm

3

/sec).

The set-up parameter 

F

 allows the user to select the ap-

propriate signal conversion function from those available:

F

 = 0: Linear characteristic (default)

F

 = 1: Square root extraction

F

 = 2: Horizontal cylindrical tank

F

 = 3...30: Look-up table with 3 to 30 pairs of values

The tables generated by functions 

F

 = 0, 

F

 = 1 and 

F

 = 2

are not  visible.  For these  functions, internal  values are
used for table computation. These values cannot be mo-
dified directly in the table by the user.

For all conversion functions, when the actual pressure is
equal  to  the 

MA

  value,  the  output  signal  will  be  at  the

lowest end  of its range (0 V, 0 mA or 4 mA). When the
actual pressure is equal to the 

ME

 value, the output signal

will be at the highest end of its range (10 V or 20 mA).
The user can enter only the 1...28 intermediate values of
the look-up table function 

F

 = 3....30. The parameters 

MA

and

ME

 relate to the start and end values of the look-up

table. A change in either of these parameter values cau-
ses the conversion function to be re-set to 

F

 = 0.

Whenever  the  value  of 

F

  is  changed,

the  instrument  internally  generates  a
new  look-up  table.  All  previous  table
values  are  deleted  and  replaced  by
new linear progression values.

5.3.7. Look-up Table Programming (F = 3..30)

If the value of set-up parameter 

F

 is selected equal to or

greater than 3, a sub-menu 

LIn

 is invoked. Through this

sub-menu  all  the  required  look-up  table  values  can  be
entered, except the first and last pairs of table values (re-
spectively corresponding to 

MA

 and 

ME

). This sub-menu

has its own entry and exit points, the latter being the last
of the value pairs to be entered. The table is stored only
when the user exits to the sub-menu prompt 

LIn

, by pres-

sing

û

. If the table is not correctly entered, the display

will indicate 

Err

, indicating an error condition. If this hap-

pens, it is not possible to exit this sub-menu mode until
the error is corrected.

Contact: EK Engineering (India)
Web: www.ekeindia.com
Email: [email protected]

All manuals and user guides at all-guides.com

Содержание DE45 series

Страница 1: ...d inspection of this product must have the qualifications training and experience necessary to carry out such work on this type of equipment Qualified personnel are people who are able to ju dge deleg...

Страница 2: ...applies to the use of unautho rized spare parts for repair maintenance of the product Any modifications to this product if and as necessary should be done only by Fischer Mess und Regeltechnik GmbH 1...

Страница 3: ...ing system must meet specifications for zone 2 class 3 Electrical connections must comply with relevant international and local regulations and norms re lating to electrical and instrumentation instal...

Страница 4: ...lighted symbols to the right of the digital dis play To change the unit of measurement first press then search for parameter EIN using Next press again and select another unit of measurement using or...

Страница 5: ...ut signal value set as parameter oEr However it should be understood that not all instrument fault and er ror conditions can be detected and signaled by the self diagnostic functions of the instrument...

Страница 6: ...ast significant right most digit The value of the set up parameter R1D determines the delay time for switching output 1 after the measured value reaches the switching point The delay value can be sele...

Страница 7: ...e measured variable corresponding with the minimum value of the output signal 0 V 0 mA or 4 mA depending on the instrument version ME Measuring range end point The value of the measured variable corre...

Страница 8: ...the instruments Inspection and test schedules depend on operating and site conditions The operating manuals of other equip ment to which the transmitter is connected must be read thoroughly to ensure...

Страница 9: ...20 70 C IP 65 acc to DIN EN 60529 Electrical Data Nominal supply voltage Operating supply voltage Output signal 24 V DC AC 12 32 V DC AC 0 20 mA 4 20 mA 0 10 V DC 3 wire Output signal load For output...

Страница 10: ...h 1 2 activation point de activation point response time delay 0 0 100 0 secs logic N O or N C Measurement unit selection mbar Pa free unit start value end value and decimal place for free unit Zero s...

Страница 11: ...ge output 0 10 V DC linear 3 wire C Current output 4 20 mA linear 3 wire P Supply Voltage 24 V DC AC nominal 12 32 V DC AC K Display Switching output 3 digit LED 2 potential free semiconductor switch...

Страница 12: ...12 14 Declaration of Conformity Contact EK Engineering India Web www ekeindia com Email india eke gmail com All manuals and user guides at all guides com...

Отзывы: