FISCHER DE45 series Скачать руководство пользователя страница 3

3

display, controls the two limit detection relays / switches,
and transmits the measured value through an analogue
conversion stage as a voltage or current signal output.

4.

Installation 

The electronic module is mounted on a flat plate or panel,
for which it has 4 holes at the rear for self-tapping screws

3.5mm.

A wall-mounting rear adaptor plate is available as an op-
tion (s. 13. Ordering Code).

The  pressure  transmitters  are  calibrated  at  the  factory
while  mounted  vertically,  pressure  ports  downward.
However, they can be mounted in any orientation. If they
are  installed  with  any  orientation  other  than  vertical
(pressure ports downward), the zero point must be re-set
(s. 5.3.2.).

IP65 protection for the housing is guaranteed only if suit-
able connecting cable is used. 

4.1.

Process Connection

Only qualified technicians authorized for this type of
work should undertake installation.

Ensure  that  process  equipment  and  pressure  lines
are at atmospheric pressure before making pressure
connections.

The instrument should be provided with suitable pro-
tection  against  pressure  surges  (e.g.,  snubber  or
pulsation damper).

Ensure that the mechanical configuration and mate-
rials of construction of the instrument are compatible
with the process media.

Ensure that process pressure is always less than the
specified safe pressure rating.

Carefully check the pressure-tightness of all pressure
connections before start-up.

4.2.Electrical Connection, 
Safety Precautions for 
Explosion Prevention

Only qualified technicians authorized for this type
of work should undertake installation.

Switch  off  electrical  power  to  the  plant  before
attempting electrical installation work of any kind.

Do not disconnect plug live wire.

To  ensure  safe  operation  supply  wiring  system
must  meet  specifications  for  zone  2,  class  3.
Electrical connections must comply with relevant
international and local regulations and norms re-
lating  to  electrical  and  instrumentation  installa-

tions  in  hazardous  areas  (e.g.:  EN 60079-14,
EN 50014).

Operating supply voltage (24 V DC/AC) must not
excess 32 V DC/AC - neither per temporary inter-
ferences!  Supply  wiring  system  must  be  pro-
tected by Si 315 T.

For  recommended  current  supply  see  11.
Specifications.

Parametrisation  by  PC  serial  interface  adaptor
EU03.F300 is permitted only in safe areas outside
explosion-hazardous areas zone 2. 

5.

Commissioning

Power  supply  and  signal  cabling  to  the  transmitter
must be correctly selected to meet operational requi-
rements, and installed in a way that does not cause
physical stress to the instrument.

Pressure  lines  must  have  a  downward  gradient
throughout from  the  pressure instrument  to  the  pro-
cess vessel / pipe. This is to prevent formation of air /
gas pockets (for liquid applications) and liquid plugs
(for  air  /  gas  applications).  If  this  continuous  down-
ward  gradient  cannot  be  provided  for  any  reason,
then  suitable  water  and  /  or  air  separation  devices
must be inserted into the pressure lines.

Pressure lines must be kept as short as possible and
must not have short bends to avoid measurement er-
rors induced by pressure line delays.

5.1.

Pressure Connections

The instruments pressure  ports  are  marked  by  " "  and
" " symbols. For differential pressure applications the " "
port  must  be  connected to the higher  pressure  and  the
" " port should be connected to the lower pressure.

If the pressure transmitter is subjected to pressure when
it is started up, zero point checking and adjustment is not
possible. In such cases, only electrical connections of the
instrument should be made, but not the pressure connec-
tions.

5.2.

Display

Contact: EK Engineering (India)
Web: www.ekeindia.com
Email: [email protected]

All manuals and user guides at all-guides.com

Содержание DE45 series

Страница 1: ...d inspection of this product must have the qualifications training and experience necessary to carry out such work on this type of equipment Qualified personnel are people who are able to ju dge deleg...

Страница 2: ...applies to the use of unautho rized spare parts for repair maintenance of the product Any modifications to this product if and as necessary should be done only by Fischer Mess und Regeltechnik GmbH 1...

Страница 3: ...ing system must meet specifications for zone 2 class 3 Electrical connections must comply with relevant international and local regulations and norms re lating to electrical and instrumentation instal...

Страница 4: ...lighted symbols to the right of the digital dis play To change the unit of measurement first press then search for parameter EIN using Next press again and select another unit of measurement using or...

Страница 5: ...ut signal value set as parameter oEr However it should be understood that not all instrument fault and er ror conditions can be detected and signaled by the self diagnostic functions of the instrument...

Страница 6: ...ast significant right most digit The value of the set up parameter R1D determines the delay time for switching output 1 after the measured value reaches the switching point The delay value can be sele...

Страница 7: ...e measured variable corresponding with the minimum value of the output signal 0 V 0 mA or 4 mA depending on the instrument version ME Measuring range end point The value of the measured variable corre...

Страница 8: ...the instruments Inspection and test schedules depend on operating and site conditions The operating manuals of other equip ment to which the transmitter is connected must be read thoroughly to ensure...

Страница 9: ...20 70 C IP 65 acc to DIN EN 60529 Electrical Data Nominal supply voltage Operating supply voltage Output signal 24 V DC AC 12 32 V DC AC 0 20 mA 4 20 mA 0 10 V DC 3 wire Output signal load For output...

Страница 10: ...h 1 2 activation point de activation point response time delay 0 0 100 0 secs logic N O or N C Measurement unit selection mbar Pa free unit start value end value and decimal place for free unit Zero s...

Страница 11: ...ge output 0 10 V DC linear 3 wire C Current output 4 20 mA linear 3 wire P Supply Voltage 24 V DC AC nominal 12 32 V DC AC K Display Switching output 3 digit LED 2 potential free semiconductor switch...

Страница 12: ...12 14 Declaration of Conformity Contact EK Engineering India Web www ekeindia com Email india eke gmail com All manuals and user guides at all guides com...

Отзывы: