R1E
Switch-on point
From switching output
R1D
Switching delay
from switch output •
Value range 0.0 to 100.0s. This value
applies equally for switching on and off.
R1F
Switching function
From switching output
Values range 1,2
1 = Switching output as NO contact, 2
= Switching output as NC contact
R2A
Switch-off point
From switching output
R2E
Switch-on point
From switching output
R2D
Switching delay
from switch output •‚
Value range 0.0 to 100.0s. This value
applies equally for switching on and off.
R2F
Switching function
From switching output
Values range 1,2
1 = Switching output as NO contact, 2
= Switching output as NC contact
ON
Measuring range unit
Value range 1,2,3
The selection is illuminated on the right
of the reading. Not all basic measuring
ranges allow free switchover. The re-
spective unit size can only be selected
if the basic measuring range of the de-
vice can be shown sensibly.
MA
Start of measuring range
The measuring value is set in that the
output signal is minimal.
(e.g.: 0V, 0mA or 4mA).
ME
End of measuring range
The measuring value is set in that the
output signal is maximum.
(e.g.: 10V, or 20mA).
np
Zero-point stabilising
Value
range 0 to ⅓ of the basic meas-
uring range. The value acts symmetri-
cally around real zero.
dpf
Free unit
Decimal point position
maf
Free unit
Start of measuring range (display)
mef
Free unit
End of measuring range (display)
Of1
Offset correction measuring input 1
Value range -
⅓ FS...0... +⅓ FS
F
Characteristic curve function
Value range 0...30
0
= linear,
1
= square rooted,
2
= flat cylindrical tank
3..30 = Table
lIn
Menu jump
Submenu table processing
If F < 3 this menu item is faded out.
oG1
Limit value
Minimum output signal
OG2
Limit value
Maximum output signal
OEr
Error signal
(Output signal in error case)
res
Reset
all parameters to standard values
(specification of the standard values
per PC)
-P-
Password setting
Value range 000 to 999
Value 000 does not hold password pro-
tection.