Generator Failure
Panda PMS AGT-DC 4000 - Chapter C: Generator Failure Page 31
Change the VCS printed circiut board if the points above carries no clearance.
Überprüfen der Begrenzung der Generatorspannung
The mechanical voltage limitation must be checked regularly. The following steps have to be
done:
1. Disconnect the plug of the actuator.
Lower suspension point:
2. Switch off all load.
3. Connect an electrical ammeter.
4. Start the generator.
5. Turn the actuator manually to the lower suspension point.
6. Charge current must be <10 A, at U=U
Nenn
.
Upper suspension point:
7. Connect the load.
8. Turn the actuator by hand gradually the insertable load up to the upper susoension point.
Charge current must not lay over 140A, at U=U
Nenn
9. If deviations are determined, a new adjustment is necessary.
C.3.3 Low Generator-Output Voltage
ATTENTION! Before working on the System read the section “Safety Instructions” on
Page iv.
If the produced alternating voltage is too low, switch the load off, in order to relieve the generator.
Mostly the problem already solved. If the output voltage is still too low, even if all load is switched
off, the generator runs without load, you can assume one or more condensers are defective.