5.7.1 Instructions for the starter battery for extended downtimes
Note: Information starter battery
Starter batteries
Self-discharge of batteries is a physical and chemical
process and cannot be avoided even if the battery is
disconnected
• For extended downtimes, the battery shall be disconnected from the genset.
• Charge battery regularly. Observe instructions of the battery manufacturer.
Depending on the battery type, check the acid level before charging and refill each cell up to the marking using
distilled water as necessary.
Modern starter batteries are typically maintenance-free.
Deep discharge will damage the battery and can render it unusable.
Keep battery clean and dry. Clean battery poles (+ and -) and terminals regularly and coat with acid-free and acid-
resistant grease. During assembly, ensure good contact of the terminal connections.
General limits for lead-acid batteries:
2.1 V / cell corresponds with full battery (charged).
1.95 V / cell corresponds with empty battery - recharge.
For a 12 V battery, the following applies:
- 11.7 V lower open-circuit voltage (battery empty), recharge battery.
- 12.6 V upper open-circuit voltage (full battery) - trickle charge full battery at 13.2 V.
For a 24 V battery, the following applies:
- 23.4 V lower open-circuit voltage (battery empty), recharge battery.
- 25.2 V upper open-circuit voltage (full battery) - trickle charge full battery at 26.4 V.
These values are based on a battery temperature of 20-25°C. Observe the instructions from the battery
manufacturer.
Note: Starter battery recommendation
Fischer Panda recommends:
• Install battery circuit breaker and switch to OFF on the
machine. (Cutting the battery circuit.)
• Secure the battery plus terminal close to the battery.
• Regularly check contacts for corrosion.
5.7.2 Measures for short downtimes
Short downtime (1 to 3 months)
• Measure battery charge status based on open-circuit voltage.
• During downtimes >7 days, disconnect battery (e.g. battery main switch to position 0).
• Check the battery within 2 months and allow the engine to warm up for min. 10 min.
• Fill fuel tank to 100% (level to full).
5.7.3 Measures for medium term downtimes / hibernation
Medium term downtimes (3 to 6 months)
Содержание Panda 5000i PMS
Страница 88: ...Maintenance Instructions Seite Page 88 Kaptitel Chapter 8 Maintenance Instructions 14 7 16 ...
Страница 94: ...Generator Tables Seite Page 94 Kaptitel Chapter 9 Generator Tables 14 7 16 Fig 9 8 1 Diamensions ...
Страница 102: ...Tables Seite Page 102 Kaptitel Chapter 10 Tables 14 7 16 ...
Страница 126: ...Inverter Panda PMGi Seite Page 126 Kaptitel Chapter 11 Inverter Panda PMGi 14 7 16 Leere Seite Intentionally blank ...
Страница 148: ...Seite Page 148 Kapitel Chapter 13 General operation 14 7 16 Leere Seite Intentionally blank General operation ...
Страница 158: ...Seite Page 158 Kapitel Chapter 15 Maintenance 14 7 16 Leere Seite Intentionally blank Maintenance ...
Страница 160: ...Seite Page 160 Kapitel Chapter 16 Annex 14 7 16 Leere Seite Intentionally blank Annex ...