Installation Instructions
26.1.11
Panda_4000s_PMS_SCB_FCB_eng.R04 - Kapitel/Chapter 5: Installation Instructions Seite/Page 95
5.7.1 Electrical connection scheme
Fig. 5.7.1-1: Installation example - with separat load output
All electrical safety installations have to be made on board.
A power source selector switch must be installed between the generator (or if applicable, AC-Control box)
and the ship´s electrical supply system. This switch must used to ensure that all AC load can be switched
off at once. This switch should also be installed to keep the generator and shore (grid) power systems sepa-
rate.
Fig. 5.7.1-2: Power source selector switch
A 3-way cam-type switch should be used. This switch basic
positions: "Shore power" - "OFF" - "Generator". If an (DC-AC)
inverter is used, a fourth position will be required.
0. OFF
I. Generator
II. Shore power connection
III. Inverter
The cam-type switch must have 2 poles, so that "MP" and "phase" can be switched off.
If a 3-phase current system is also installed with the option of supplying from either the generator or shore power, an
additional switch must be installed to keep these systems separate.
1. Generator
2. Starter battery
3. Remote control panel
4. Load connection
5. Battery switch
6. Fuse
Содержание 4000s PMS FC
Страница 24: ...Seite Page 22 General R01 1 26 1 11 Leere Seite Intentionally blank General References and Regulations...
Страница 68: ...Seite Page 66 Panda_4000s_PMS_SCB_FCB_eng R04 26 1 11 Leere Seite Intentionally blank The Panda Generator...
Страница 112: ...Seite Page 110 Panda_4000s_PMS_SCB_FCB_eng R04 26 1 11 Leere Seite Intentionally blank Maintenance Instructions...
Страница 122: ...Seite Page 120 Panda_4000s_PMS_SCB_FCB_eng R04 26 1 11 Leere Seite Intentionally blank Generator Failure...