Blow-down pump
works but not wa-
ter is drained
•
Steam cylinder and/or drainage system
blocked
•
Clean cylinder base and/or
drainage system, respectively
Cylinder is fully
drained after par-
tial blow-down
despite pump
beeing switched
off
•
Vent pipe is blocked
•
Clean venting bore; replace
vent pipe, if required
No steam exit
from steam mani-
fold
•
Steam pipe improperly laid (water bag) or
blockage
•
Rerun steam hose according to
guide lines, remove blockage
Water exits peri-
odically from
drain hose with-
out pump
switched on
•
Excess pressure in duct system (max.
overpressure is 1200 Pa)
•
Lengthen drain hose system;
consult your expert dealer if
problem persists
Uneven electrode
wear
•
•
•
•
•
One or more electrodes not supplied with
power
Circuit breaker tripped
Main contactor contact not functional
Phase loading not symmetric
Electrode immersion depth differs. Unit
not mounted plumb
•
•
•
•
•
Check power supply and wiring
Check circuit breaker. Replace,
if required
Check main contactor. Replace,
if required
Ensure power supply phase ba-
lance by measurement
Check installation and correct
positioning, if required
Problem
Possible cause for faulty situation
Countermeasure