Page 25
Main screen
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
min
max
FS
[ ] refers to a related explanation of the term
1 Humidity_actual_value
Actual value [1] of rel. humidity [2] in %
2 Humidity_set_value
0
99.0
50.0
Set value [3] of RH [2] in %
7 Steam_actual_unit
Current steam output of the unit [4] in kg/h
9 Steam_output_max.
Set value of maximum output power [43]
10 Demand
The demand [5] is the control signal from which the internal actuator signal
[42] is created
11 Control_sig._internal
Internal actuator signal [42] as a percentage of the actuator signal for the
nominal output
12 Output_signal
Output signal [69] on terminals 12, 13 proportional to input signal
13 Current_actual_cyl.
1
The current power consumption of cylinder 1 (only for ELDB [77])
14 Current_actual_cyl.
2
The current power consumption of cylinder 2 (only for ELDB [77] double
cylinder units)
15 Water_level_cyl.
1
Water level in cylinder 1 in mm (only for HKDB [78])
16 Water_level_cyl.
2
Water level in cylinder 2 in mm (only for HKDB [78] double cylinder units)
20 Humidity_actual_max
Actual value [1] of rel. humidity [2] in % whwn floating max. limiter [35] is
activated
21 Humidity_set_max
5.0
99.0
80.0
Specification of max. humidity for the switch-off point when using the floating
max. limiter [35]
Read value
Read value
Read value
Read value
Read value
Read value
Read value
Read value
Adjustment/value range
Factory setting (FS) Bold
Read value
Read value
Read value
Table of the read values available in the main screen and the humidity set value