Page 54
029
Internal
•
Main board is defec-
tive
•
Replace mainboard
030
032
Filling_valve 1
Filling_valve 1 a. 2
Filling was not successful,
i.e. the expexted filling level
was not achieved after 30
mins of filling.
•
Solenoid valve or wa-
ter supply line conta-
minated or defective
•
Clean water supply
line and/or solenoid
valve; replace solenoid
valve, if defective
•
Solenoid valve defec-
tive
•
Make measurement
on solenoid; replace
solenoid valve, if de-
fective
•
Water supply not
opened
•
Open water supply
•
Solenoid valve elec-
trically not driven
- electrical cabling not
o.k.
- Mainboard relay not
energised
- Check electrical cable
and replace, if required
- Measure voltage on
mainboard terminal 11
against N; replace
mainboard, if required
•
Steam hose not laid
with sufficient incline/
decline resulting in a
water bag obstructing
steam flow. Steam
builts up pressure in
steam cylinder and
pushes water towards
drain
•
Blockage in steam
pipe impedes the
steam flow. The steam
builds up pressure in
the cylinder and press-
es the water into the
drain.
•
Check steam hose
layout. Eliminate water
bag.
•
Remove blockage in
steam pipe
•
L3 phase break-down
•
Main contactor does
not switch L3 phase
•
Reestablish L3 phase
feeding
•
Replace main con-
tactor
These icons
flash
Fa
ult
Code
Fault message
Possible cause
Countermeasure