Page 30
5.6.2 Read values submenu
04: Read_values
No. Parameter
No.
Meaning/Comment
[ ] explains the term in the glossary
min
max
FS
[ ] refers to a related explanation of the term
1 Status_unit
Operating condition of unit
0
Control performs initialisation [10]
1
Unit is ready for steam production, but the interlock (safety) system [11] is
open
2
Unit is ready for steam production, but there is no demand [5]
3 Humidifying
[47]
4
Unit has switched off after limitation of operating time was reached [32]
5
Unit was switched off via a software command [12] for opening the interlock
(safety) system [83] via the communication interface [13]
6
Steam production was switched off manually via the on/off button [14]
7
The standby heating [16] is in the heating phase
8
The standby heating [16] is in the resting phase
9
There is no demand [5] in ECO mode [61]
10
Humidifying in ECO mode [61]
11
Steam is not produced after the timer [18] has expired
13
No steam is produced after the weekly timer has run out
14
Steam production was cut via the digital input [97]
270
A service message has appeared. For detailed specification, see read value
8 for cyl. 1 and read value 9 for cyl. 2 (double cylinder units only)
900
Unit is performing diagnostics [15]
901
The control electronics is not yet programmed for the unit type
902
A USB stick was plugged in and a parameter upgrade is run by the unit
903
A parameter upgrade was successfully carried out. Restart of the unit is
required
999
There is a fault
2 Status_cyl.
1
Status of cylinder 1
0
Unit is in initialization phase
[10]
1
Cyl. 1 is ready for steam production, but the interlock (safety) system [11] is
open
2
Cyl. 1 is ready for steam production, but there is no demand [5]
3 Humidifying
[47]
30
Filling via solenoid valve 1 [19]
32
Filling via solenoid valve 1 and solenoid valve 2 [19]
60
At the start of operation, the unit performs a start blow-down [20]
61
A partial blow-down [21] is performed
62
A full blow-down [22] is performed
63
The unit performs a dilution [23] of the cylinder water (only ELDB [77])
64
The unit performs an overcurrent blow-down [24] because the measured
current is too high (only for ELDB [77])
65
The unit performs a max. level blow-down [25] because the water level is too
high (only for HKDB [78])
66
The unit performs a Standby blow-down [26], because the maximum
duration without demand [5] has been reached
67
A dead-end line flushing is performed [27]
68
A manual blow-down [28] was triggered
81
A partial blow-down [21] is performed before the next filling process
82
A full blow-down [22] is performed before the next filling process
90
The sensor electrode reports when the maximum water level in the cylinder
has been reached (only for ELDB [77])
270
A service message has appeared. For detailed specification, see read value
8 for cyl. 1 and read value 9 for cyl. 2 (double cylinder units only)
900
The unit is in diagnostic mode [15]
999
There is a fault
3 Status_cyl.
2
Status of cylinder 2 (as cylinder 1)
4 Fault_message_unit
List of possible unit fault messages
5 Fault_message_cyl.
1
List of possible fault messages for cylinder 1 (see Fault_message_unit)
Read value
Diagnosis
Fault
Read value
see: 04-2 Status_cyl. 1
Read value
see: 02-1 Fault_message_unit
Dead_leg_flushing
Manual_blow-down
Part._blow-down_pending
Full_blow-down_pending
Cylinder_full
Service_message
Part._blow-down
Full_blow-down
Dilution
Max._current_blow-down
Max._level_blow-down
Standby_blow-down
Safety_interlock_open
No_Demand
Humidification
Filling_valve 1
Filling_valve 1 a. 2
Start_blow-down
Not_programmed
Update_in_progress
Restart
Fault
Read value
Initialization
Humidification_ECO
Timer_steam_off
Weeckly_timer_steam_off
Digital_input_steam_off
Service_message
Diagnosis
Runtime_limitation
Remote_off
No_bus-signal
Standby_heating_heating
Standby_heating_interval
No_demand_ECO
Factory setting (FS) Bold
Read value
Initialization
Safety_interlock_open
No_Demand
Humidification
Adjustment/value range
Read values
6 Fault_message_cyl.
2
List of possible fault messages for cylinder 2 (see Fault_message_unit)
8 Service_message_cyl.
1
List of service messages for cylinder 1
9 Service_message_cyl.
2
List of service messages for cylinder 2
Read value
see: 02-5 Service_message_cyl. 1
see: 02-2 Fault_message_cyl. 1
Read value
see: 02-2 Fault_message_cyl. 1
Read value
see: 02-5 Service_message_cyl. 1