![fisair CCE2.0 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/fisair/cce2-0/cce2-0_installation-and-operation-manual_2294088039.webp)
MANUAL for the Stages Control Panel | CCE2.0
39
8.6.2. BACnet/IP:
Pay attention to the following screens that the Display shows regarding this type of communication:
❖
BACNET UDP Port: Select the address of the Bacnet UDP Port. By default it is 47808.
❖
Bacnet Device number: Select the BACnet device number. By default it is 1234.
Protocolo BACnet/ IP Protocol:
•
Type: Bacnet/IP over Udp
•
Connect the Ethernet cable to the SEF-029 card before starting the Disconnector I1. The
LEDs for connection (yellow) and communication (green) are not currently available.
The default IP address is 10.42.0.100
•
The foreign device must be registered as follows:
Remote BBMDIPv4.IPv6 Endpoint = 10.42.0.100:47808
Mapping for BACnet communication protocols:
Write:
The following table shows the write function of each communication object:
Object
Description
Writing
SET OnOff Auto*
(Analog_Output:0)=1010
Write position disconnector
switch I1
0
→
OFF, 1
→
ON, 2
→
AUTO(Subject
to interlocking function in J21)
SET V CONTROL
Analog_Output:12 =1060*
Write analogue signal
0-10 VDC step control
Write range 0-10.
SET V OR mA
(Analaog_Output:11)= 1061
Select if the steps are
regulated by
Volts (0
→
V) or amperes (1
→
A)
SET mA CONTROL
(Analog_Output:13)=1062*
Write analogue signal 4-20
mA step control
Write range 4-20
SET DRAIN CONFIG.
(Analog_Output:14)=1064
Write signal configuration
empty
0
→
Never, 1
→
Standard, 2
→
Conductivity control
SET_LANGUAGE
(Analog_Output:16)=1070
Write Language
0
→
Spanish 1
→
English 2
→
German
3
→
French
RESET DEF. VALUES
(Analog_Input:14)
Reset to factory default
values
Key required for reset 1997
SET EMERGENCY J20
(Analog_Output:17)
Activates the alarm signal
0
→
Alarm Off
1
→
Alarm On
* These objects are bidirectional: In addition to working as writing, they show the reading of their
states.
Содержание CCE2.0
Страница 2: ...MANUAL for the Stages Control Panel CCE2 0 2 ...
Страница 11: ...MANUAL for the Stages Control Panel CCE2 0 11 5 Hardware description Figure 3 1 CCE2 0 front cover ...
Страница 13: ...MANUAL for the Stages Control Panel CCE2 0 13 Figure 3 3 CCE2 0 Open location SEF 028 1 and SEF 032 1 v2 cards ...
Страница 14: ...MANUAL for the Stages Control Panel CCE2 0 14 Figure 3 4 Inside cover CCE2 0 standard ...
Страница 53: ...MANUAL for the Stages Control Panel CCE2 0 53 13 Declaration of conformity 13 1 D C Machine ...
Страница 54: ...MANUAL for the Stages Control Panel CCE2 0 54 13 2 D C Partly completed machinery ...
Страница 55: ...MANUAL for the Stages Control Panel CCE2 0 55 14 Warranty ...
Страница 56: ...MANUAL for the Stages Control Panel CCE2 0 56 ...
Страница 57: ...IÓN F ...
Страница 58: ...IÓN ...
Страница 59: ...IÓN MAN P Ev1 Mv1 P P ...
Страница 60: ...F IÓN ...
Страница 61: ...IÓN ...
Страница 62: ...IÓN MAN P Ev1 Mv1 P P ...