MANUAL for the Stages Control Panel | CCE2.0
31
8.1.2. Standard emptying:
Complete emptying of the basin depends on the following Timers*:
❖
Timer T05 (Min. NEVER / Max. 24h)
While the equipment is running, it is fully emptied periodically
according to the time value set in T05.
❖
Timer T06 (min. 0 h / Max. 24h)
The delay time for complete emptying is set according to the
time value in T06, with the equipment switched off.
8.1.3.
No emptying (never):
The basin is never emptied
*These Timers are configured in chapter
“Settings”.