Operation Manual
FW-1200-M
© 2012
First Water Systems, Inc
pg. 8
3.5 Operation
Once water is flowing, very little maintenance is required. Someone
should be present to monitor the following:
Source water does not deplete.
Clean water storage does not overflow.
Water flow does not stop.
Filters needing to be changed.
Pausing Operation
The FW-1200-M may be turned off and on throughout an event. To
stop the flow of water, turn Main Valve to the off position. The
Pressure Switch on the Pump will automatically stop the pump
motor. If desired, you may turn off the power to the Filtration Unit to
shut off the UV Lamp.
If the system will be down for more than 4 hours, flush with clean
water for 1 minute before turning off. Do not leave standing water in
the unit for more than 36 hours.
Resuming Operation
After a pause in operation, the system may be restarted by turning
all power back on and opening the Main Valve. It may be necessary
to re-prime the Pump and bleed air from the system. It may be
necessary to reset the Pump by pressing the Reset button on the
Pump.
Filter Maintenance During Operation
Filter life will vary greatly based on the turbidity of source water.
Under optimal water conditions, a complete filter set should be
replaced every 50,000 gallons. Optimal water conditions are defined
as micro-biologically contaminated water sources with low levels of
sediment, turbidity or tannins. Increased levels of sediment,