53
®
Option 03.6 - Limit Modulation Range (0/1)*
By default, the unit modulates the burner between the set points P3 (low fire) and Px (high fire),
where Px is the last setpoint entered in commission ratio mode. If oxygen trim is fitted, it is not pos-
sible for any drive position to be trimmed lower than point P3 (low fire) or higher than point Px
(high fire).
This option parameter allows the normal modulation range of the burner to be limited so that the
burner may only modulate between points P4 (one setpoint above low fire) and Px-1 (one setpoint
below high fire). Since oxygen trim is not affected by this limitation, each drive may be trimmed
between the points P3 and Px. This means that it is not possible to over-fire or under-fire the burner
but full trim may still be achieved at high and low fire.
0
-
Not limited. Burner modulates from P3 to Px
Oxygen trim works over full range from P3 to Px
1
-
Normal modulation range limited to P4 to Px-1
Oxygen trim works over full range from P3 to Px.
Option 03.8 - Reset hours run (0/1)*
This option parameter allows the HOURS RUN display for all fuels to be reset to zero. To perform a
reset, set this option parameter to 1 and leave setup mode. The HOURS RUN display will reset and
this option parameter will automatically be set back to 0.
Options 04.1 to 06.5 - Drive output mapping (0 – 12)*
Each drive shown on the display may be mapped to a particular output. See section 8.2 for a dia-
grammatic explanation.
If a drive is not required (such as fuel 2 on a single fuel burner) then its mapping value should be set
to zero. If a drive is required, then its corresponding mapping value should be set to a value between
1 and 12, which then maps that drive to the specified output (see table below).
OUTPUT NO.
OUTPUT
CONNECTOR
0
No drive required
Output
Feedback Input
1
Basic drive board, motor output 1
PE2-PE3
PD16-PD18
2
Basic drive board, motor output 2
PE4-PE5
PD11-PD13
3
Basic drive board, motor output 3
PE7-PE8
PD8-PD10
4
Basic drive board, motor output 4
PE9-PE10
PD2-PD4
5
Isolated drive board 1, motor output 1,
PF7-PF8
PG8-PG10
6
Isolated drive board 1, motor output 2,
PF5-PF6
PG3-PG5
7
Isolated drive board 2, motor output 1
PJ7-PJ8
PK8-PK10
8
Isolated drive board 2, motor output 2
PJ5-PJ6
PK3-PK5
9
Isolated drive board 1, inverter 4-20mA 1
PH4-PH5
PH11-PH12
10
Isolated drive board 1, inverter 4-20mA 2
PH2-PH3
PH9-PH10
11
Isolated drive board 2, inverter 4-20mA 1
PL4-PL5
PL11-PL12
12
Isolated drive board 2, inverter 4-20mA 2
PL2-PL3
PL9-PL10