13
®
Pressure/Temperature Sensor Input
The pressure/temperature cabling
must be overall shielded 3-conduc-
tor Belden 8735 or similar. Since
this cable may be run in conduit
with high voltage wiring, its voltage
rating must exceed the maximum
voltage carried by any other cable
in the same conduit.
The input is suitable for use with 0-5V
or 4-20mA signals (externally or inter-
nally powered), the PXMS-XXX steam
pressure sensor, or a three wire resis-
tance thermometer.
Refer to the option links section for
details on setting the correct voltage
and input type.
Connect the cable shield to the controller with the use of the clamping bar.
Make all connections at the sensor/transmitter first.
SENSOR SUPPLY PA16
SENSOR IN PA17
SENSOR GND PA18
CABLE
CLAMP
Fireye PXMS-XXX
SENSOR
+ -
OR EXT. SELF-
POWERED
4-20mA /0-5V
5/20V
+
-
CABLE
CLAMP
SENSOR GND PA18
SENSE RTD PA19
RTD SUPPLY PA20
3 – WIRE
RESISTANCE
THERMOMETER