background image

5

®

Cables, FX04-1

Cord sets having female connectors on both ends are available in 6 and 40 foot lengths.

Field wirable cables and connectors, FX04

Loosen the four cross-head housing cover screws and pull the cover hard to remove it. For the elec-
trical installation of the FX04 servo motor, use the prescribed cable type (corresponding to the envi-
ronmental conditions).

Feed cables through screwed cable entry via suitable conduit and glands and place the stripped ends
of the leads into screw connection terminals and terminate. Cable type 59-565 contains a drain wire,
and care should be taken when routing this to terminal 3. Tubing over the drain wire is recom-
mended. Wire ends should be properly stripped such that no bare wires protrude from the terminals
and thus produce the risk of a current surge or of a short circuit.

Store the cables such that they are not pinched when the housing cover is fitted or interfere with the
end travel switchcam mechanism or potentiometer coupling shaft.

Wiring information using 59-565

Terminal

Color

Description

1

Brown

RS485 B(-)

2

Black

24 VDC 

Return

3

Drain

Earth 

Ground

4

Orange

RS485 A(+)

5

Red

24 VDC 

Power

Note: Brown and Orange are a twisted pair.

Red and Black are 18 AWG

59-565-6 or 59-565-40

1 1 4 4 2 2 5 5 


Cable Entry

(suitable conduit

fitting required)

Содержание NEXUS FX04

Страница 1: ...er as long as the output torque is suited to the application Before attempting to install commission or operate this equipment all relevant sections of this docu ment must be read and fully understood...

Страница 2: ...C operation 4Nm 3 lb ft torque with connectors minimum travel time of 30 seconds for 90 FX20 Servo motor 24 VDC operation 20Nm 15 lb ft torque without connectors accepts 1 2 inch NPT fitting minimum t...

Страница 3: ...ried out only by a licensed electrician or a qualified person having adequate training who is aware of potential hazards Wiring Five wires must be connected to power the servo Cordsets are available f...

Страница 4: ...haft should be connected using a suitable arm link or flexible coupling The mounting position of the FX04 servo motor is arbitrary FIGURE 2 DIMENSIONS FX04 SERVO MOTOR 1 38 34 9 32 8 4 47 113 5 3 27 8...

Страница 5: ...ns a drain wire and care should be taken when routing this to terminal 3 Tubing over the drain wire is recom mended Wire ends should be properly stripped such that no bare wires protrude from the term...

Страница 6: ...on and Safety Advice sec tions must be read Note The cover must be removed to make the following adjustments Unit Address The servos use a Modbus compatible communications protocol via RS485 The baud...

Страница 7: ...e returned to the Modbus controller The number written to the register can range from 0 to 1100 representing the full range of the servo 110 degrees in tenths of a degree For example writing a 450 to...

Страница 8: ...32767 to 32768 6 last ROM CRC of servo software 0x0000 to 0xFFFF Table 3 Actuator Error Codes Error Code Description Possible Remedies 0 No error actuator is running normally 1 7 Internal CPU self che...

Страница 9: ...9 Blank Page...

Страница 10: ...defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MA...

Отзывы: