5
®
Cables, FX04-1
Cord sets having female connectors on both ends are available in 6 and 40 foot lengths.
Field wirable cables and connectors, FX04
Loosen the four cross-head housing cover screws and pull the cover hard to remove it. For the elec-
trical installation of the FX04 servo motor, use the prescribed cable type (corresponding to the envi-
ronmental conditions).
Feed cables through screwed cable entry via suitable conduit and glands and place the stripped ends
of the leads into screw connection terminals and terminate. Cable type 59-565 contains a drain wire,
and care should be taken when routing this to terminal 3. Tubing over the drain wire is recom-
mended. Wire ends should be properly stripped such that no bare wires protrude from the terminals
and thus produce the risk of a current surge or of a short circuit.
Store the cables such that they are not pinched when the housing cover is fitted or interfere with the
end travel switchcam mechanism or potentiometer coupling shaft.
Wiring information using 59-565
Terminal
Color
Description
1
Brown
RS485 B(-)
2
Black
24 VDC
Return
3
Drain
Earth
Ground
4
Orange
RS485 A(+)
5
Red
24 VDC
Power
Note: Brown and Orange are a twisted pair.
Red and Black are 18 AWG
59-565-6 or 59-565-40
1 1 4 4 2 2 5 5
3
3
Cable Entry
(suitable conduit
fitting required)
Содержание NEXUS FX04
Страница 9: ...9 Blank Page...