The installer should be satisfied that, as a result of the mounting, the commissioning or as a result of
the test adjustments on the actuator, no potential hazards will be produced for devices/machines/
plant.

Before mounting the servo motor, check the free movement of the valve/device.

After completing the mounting and adjustment, check the correct functioning of the servo motor.   

Safety advice for mounting and adjustments

The installer must be satisfied that, as a result of the commissioning or the test adjustments on the
servo motor, no potential hazards will be produced for personnel or the environment.

After completing adjustments check the correct functioning of the servo motor.

Check the correct functioning of any safety devices.

Carry out adjustments only in accordance with the instructions described in this documentation.

Adjustments must therefore be carried out only by a licensed electrician or a qualified person having
adequate training, who is aware of potential hazards.

Wiring

Five wires must be connected to power the servo. Cordsets are available for the FX04-1. Field
wirable connectors and cable are available for the FX04 (see page 5). Be sure to connect the ground
connection first to eliminate the ESD (electro static discharge) potential.

Use in a PPC4000 System

On a previously commissioned system, care must be taken when replacing a servo motor believed to
be defective. Although every effort is made to calibrate each servo, there may be slight differences
from servo to servo. It is strongly recommended the installer, equipped with a combustion analyzer,
use ADJUST RATIO to step through each profile that uses the replacement servo. Each profile set-
point should be checked and adjusted for proper combustion.

SERVO MOTOR DESCRIPTION

FIGURE 1.

UNIT ADDRESS

MANUAL MOVEMENT

MOUNTING SURFACE

OUTPUT SHAFT

PLASTIC COVER

MOUNTING HOLES (4)

FX04-1 Shown

CCW

CW

90°

clockwise
rotation shown
as viewed from
the cover side

Содержание NEXUS FX04

Страница 1: ...er as long as the output torque is suited to the application Before attempting to install commission or operate this equipment all relevant sections of this docu ment must be read and fully understood...

Страница 2: ...C operation 4Nm 3 lb ft torque with connectors minimum travel time of 30 seconds for 90 FX20 Servo motor 24 VDC operation 20Nm 15 lb ft torque without connectors accepts 1 2 inch NPT fitting minimum t...

Страница 3: ...ried out only by a licensed electrician or a qualified person having adequate training who is aware of potential hazards Wiring Five wires must be connected to power the servo Cordsets are available f...

Страница 4: ...haft should be connected using a suitable arm link or flexible coupling The mounting position of the FX04 servo motor is arbitrary FIGURE 2 DIMENSIONS FX04 SERVO MOTOR 1 38 34 9 32 8 4 47 113 5 3 27 8...

Страница 5: ...ns a drain wire and care should be taken when routing this to terminal 3 Tubing over the drain wire is recom mended Wire ends should be properly stripped such that no bare wires protrude from the term...

Страница 6: ...on and Safety Advice sec tions must be read Note The cover must be removed to make the following adjustments Unit Address The servos use a Modbus compatible communications protocol via RS485 The baud...

Страница 7: ...e returned to the Modbus controller The number written to the register can range from 0 to 1100 representing the full range of the servo 110 degrees in tenths of a degree For example writing a 450 to...

Страница 8: ...32767 to 32768 6 last ROM CRC of servo software 0x0000 to 0xFFFF Table 3 Actuator Error Codes Error Code Description Possible Remedies 0 No error actuator is running normally 1 7 Internal CPU self che...

Страница 9: ...9 Blank Page...

Страница 10: ...defective in material or workmanship or which otherwise fails to conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MA...

Отзывы: