37
®
Notes on operation:
While in AUTO or RUN mode, once the action initiated by T16 begins, it cannot be reversed by
opening T16. At the conclusion of PTFI, if T16 is open, the control will advance through MTFI to
AUTO.
If START INPUT (T21) and PILOT HOLD (T16) are both active in AUTO, T16 has priority and
revert to pilot will be initiated.
The user shall contact the burner manufacturer to determine if the pilot assembly is rated
for intermittent operation.
?