27
®
SYSTEM INFO SUB-MENU
The sub-menu "SYSTEM INFO" allows the user to review information pertaining to the operation
of the control (e.g. average main flame signal strength, status of the high fire and low fire end
switches, etc.). This information can be very helpful when setting the damper linkages on the firing
rate motor. The user may also clear the internal burner history (burner hours, cycles and system
hours), number of lockouts and stored lockout information.
Language choices of English, French, Spanish, Dutch and Swedish are available.
The MODE key is used to enter and exit the "SYSTEM INFO" sub-menu, and the NEXT and BACK
keys are used to advance through the sub-menu.
SYSTEM OPERATION
The programmer module determines the functional operation of the Burnerlogix control (e.g. purge
timing, trial for ignition timings, recycle or non-recycle operation, etc.). For purposes of illustration,
we will be looking at the YP100 Programmer functions and messages associated with the BLL510
display module in this bulletin.
Because the messages change depending upon which YP style
programmer is being used, it is necessary to check the bulletin covering the specific program-
mer for exact details.
Refer to the suggestions shown in this bulletin before proceeding to power the
Fireye YB110 (YB230) BurnerLogix system. Items such as scanner installation, short circuit tests
and safety information should be carefully reviewed.
P
START HERE
MODE
STANDBY
M-D LIMIT
OPEN
PRESS
KEY FROM MAIN MENU LOOP
STANDBY
M-8 LIMIT
OPEN
STANDBY
MDFY TO CHANGE
LANGUAGE ENGLISH
MDFY TO CHANGE
CLEAR HISTORY NO
MODE
PRESS
KEY AT ANYTIME TO EXIT SUB-MENU
AVG. MAIN FLM 42
STANDBY
AVG. PILOT FLM 42