FIGURE 2.
Temperature Sensor - TS350-2, TS350-4, TS350-8
FIGURE 3.
Temperature Sensor - TS752-2, TS752-4, TS752-8
0.625”
X = 2”, 4” or 8”
11.0” [279]
7.5” [191]
WARNING:
1.
Read these instructions carefully. Failure to follow them could result in a hazardous or
dangerous condition.
2.
Insure that the range of the selected sensor is appropriate for the application. Note: A
general rule to follow when selecting the sensor range is that the expected value of the
monitored pressure or sensor should fall between 40-70% of the upper range of the sensor.
For example, a steam boiler maintains 20 lbs. pressure, select the BLPS-30 Pressure Sensor,
with a 0-30 PSIG range
3.
The sensors must be located where the ambient temperature will not exceed the maximum
ambient operating temperature specified for the sensor.
4.
Insure that the pressure range programmed on the BurnerLogix Boiler Room Control
matches the installed pressure sensor. Refer to Bulletin BLZ-1001.
5.
Do not mount any of the sensors where they could be used as a footstep.
6.
Installation must be performed by a trained, experienced flame safeguard technician.