MOUNTING PRESSURE SENSORS

Note: Refer to Figure 4.

1.

The steam pressure sensors (BLPS-15, -25, -30, -200, -300) provide a 1/4” NPT male fitting for
connection to the steam header. Included is a 1/4” coupling.

2.

Make sure the boiler is shut down and zero steam pressure exists in the boiler vessel.

3.

Disconnect power to the boiler controller so the boiler cannot sequence during installation of the
steam pressure sensor.

4.

Always mount the steam pressure sensor 

above the water line

 of the boiler.

5.

Locate the pressure sensors where the ambient temperature will not exceed 185F

FIGURE 4.

6.

Although the unit can withstand substantial vibration without damage or significant output
effects, it is good practice to mount the pressure sensor where there is minimum vibration.

7.

A steam trap (siphon loop)

 must be connected 

between the boiler and the pressure sensor to pre-

vent boiler scale and corrosive vapors from affecting the pressure sensor element.

8.

Use only a small amount of pipe compound to seal the connection joints. Excess pipe compound
may clog the fitting and prevent proper operation of the sensor.

9.

Make all pipe connections in accordance with approved standards.

10.

When tightening the sensor, apply a wrench to the hex flats located just above the pressure fit-
ting.

 DO NOT

 tighten by using a pipe wrench on the housing. Do not tighten the pressure sensor

by hand.

MOUNTING TEMPERATURE SENSORS

The immersion style temperature sensors have a ½" NPT mounting for the 2", 4" and 8" thermowell
probes, and a ½" conduit fitting.

HOT WATER

Note: Refer to Figure 4

1.

Disconnect power to the boiler controller so the boiler cannot sequence during installation of the
hot water temperature sensor.

2.

The thermowell must be mounted where it is always exposed to the circulation of the hot water

3.

If the water system is full, drain the system below the point where the thermowell will be
installed.

4.

Tap an appropriate size fitting. (2", 4" and 8" thermowell have ½"NPT fitting).

5.

Insert the appropriate thermowell (2", 4", or 8") and tighten.

6.

Fill the system to check for leakage.

WARNING: The electro-mechanical high steam limit and/or high hot water temperature
limit MUST REMAIN in the running interlock circuit of the flame safeguard control. 

STEAM PRESSURE

OR HOT WATER SENSOR

ELECTRO-MECHANICAL

HIGH LIMIT

(STEAM OR WATER)

Содержание BLPS-25

Страница 1: ...rature Sensors have a 1 2 NPT mounting for the 2 4 and 8 thermowell probe The pressure and temperature sensors provide a 4 20 mA control signal over their respec tive stated ranges to the PPC4000 and BurnerLogix Control systems No setting or calibra tion is required for either type of sensor The PPC4000 and BurnerLogix Control systems perform continuous safety checks on the operation of all pressu...

Страница 2: ...ns and conduit adapter cover BLPS 200 Pressure transducer 0 to 200 psi 0 to 13 8 Bar 4 20 mA output linear with pressure NPT mount ing Screw terminal connections and conduit adapter cover BLPS 300 Pressure transducer 0 to 300 psi 0 to 20 7 Bar 4 20 mA output linear with pressure NPT mount ing Screw terminal connections and conduit adapter cover TS350 2 Temperature sensor Range 32 F to 350 F 0 C to...

Страница 3: ...7 Controls Primary Safety Component MCCZ7 File MP1537 Controls Primary Safety Certified for Canada MCCZ8 File MP1537 Controls Primary Safety Certified for Canada Component Factory Mutual FM Class 7610 Acceptable by Industrial Risk Insurers I R I FIGURE 1 Pressure Sensor BLPS 15 25 30 200 300 COM OUT GND EXC ...

Страница 4: ...ored pressure or sensor should fall between 40 70 of the upper range of the sensor For example a steam boiler maintains 20 lbs pressure select the BLPS 30 Pressure Sensor with a 0 30 PSIG range 3 The sensors must be located where the ambient temperature will not exceed the maximum ambient operating temperature specified for the sensor 4 Insure that the pressure range programmed on the BurnerLogix ...

Страница 5: ...he fitting and prevent proper operation of the sensor 9 Make all pipe connections in accordance with approved standards 10 When tightening the sensor apply a wrench to the hex flats located just above the pressure fit ting DO NOT tighten by using a pipe wrench on the housing Do not tighten the pressure sensor by hand MOUNTING TEMPERATURE SENSORS The immersion style temperature sensors have a NPT m...

Страница 6: ...sensor if provided by the boiler man ufacturer 2 If no well connection is provided select an appropriate location for mounting the temperature sensor Preferably as close to the boiler outlet as possible OUTDOOR AIR TEMPERATURE 1 The outdoor air temperature sensor should be mounted on the outside of the building where it will be exposed to representative air temperature but not to direct sunlight A...

Страница 7: ... separate conduit DO NOT install sensor wiring in any conduit or junction boxes with high voltage wiring 6 Maximum wiring distance for sensor wiring is 100 feet 7 See Table 1 for wiring terminations to the Burnerlogix 8 See Table 2 for wiring connections to the PPC4000 TEMPERATURE SENSORS 1 All wiring must be in accordance with National Electrical Code and local codes ordinances and regulations 2 ...

Страница 8: ... conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANT ABILITY OR ANY OTHER WARRANTY EXPRESS OR IMPLIED Except as specifically stated in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively...

Отзывы: