60-2991-1 Wiring
Honeywell Term
Function
BurnerPro Term
4
Line Voltage Supply
1 & 4
1
L2
Line Voltage Common
2
F
Flame Rod
2
24
G
Flame Rod Ground
Earth Ground
UV Scanner
2
22
2
UV scanner
2
23
2
6
Operating Control & Limits
5
20
Proof of Closure Valve
12
7
Running Safety Interlock (Air Flow)
3
14
3
10
Ignition Transformer
16
8
Interrupted Pilot Fuel Valve
17
21
Intermittent Pilot Valve
18
9
Main Fuel Valve
19
5
Blower Motor
6
18
Low Fire Start Switch
8
19
High Fire Start Switch
15
3
Alarm
3
12
High Fire
Internal relays
4
13
Common
Internal relays
4
14
Low Fire
Internal relays
4
15
Auto
Internal relays
4
22
Shutter
Not used
1
Terminal 4 is internally jumpered to terminal 1 via the BurnerPro control.
2
If the Honeywell control used a non-self check UV scanner, then the Honeywell scanner must be removed and the Fireye UV
scanner must be wired into terminals 22 and 23 on the BurnerPro wiring base.
3
The BurnerPro will lockout when the Running Safety Interlock circuit opens (RM7800L)
4
The BurnerPro outputs 120 VAC to the Mod Motor circuit. The 60-2991-1 adapter provides relays to simulate the dry contact
Mod Motor outputs of the RM7800.