© 2021 Carrier
3
SPECIFICATIONS
MODEL
:
60-2991-1: HW RM7800 series burner controls with modulating motor control (RM7800/RM7840/RM7845 less
valve proving).
60-2991-2: HW RM7800 series burner controls with on/off motor control (RM7895).
BURNERPRO SYSTEM SPECIFICATION
Supply Voltage:
BP110 110 VAC (+20%, -15%) 50/60 Hz, single phase
Power Consumption:
7 VA
Temperature Rating:
Operating: -40°C to +60°C (-40°F to 140°F)
Storage: -50°C to +85°C (-58°F to 185°F)
Flame Amplifier Rating:
UV: Terminals 22 & 23, 300VDC/ 3mA
FR: Terminals 24 & Earth, 330VAC (max), 3uA min/10uA max flame current
Protection Category:
IP40 standard version
Control Dimensions:
With wiring base (60-2981-1 or -2); 4.15” L x 4.15" W x 5.0" H (105mm x 105mm x 127mm)
Shipping Weight:
Approx. 1.3 lbs. (0.6 kg)
Relative Humidity:
90% R.H. (Non-Condensing)
OPERATING TEMPERATURE LIMITS
CONTROL
MAXIMUM
MINIMUM
BP110
140°F
60°C
-40°F
-40°C
UV90L-1
194°F
90°C
-40°F
-40°C
UV1AL-3, -6
200°F
94°C
-40°F
-40°C
UV5-1, UV5-2
140°F
60°C
-4°F
-20°C
LOAD RATINGS:
Terminal
Typical Load
Maximum Rating
@120V-50/60 Hz
Maximum Rating
@230V-50/60 Hz
Alternate Rating
6-7
Burner/Blower
Motor
2 F.L.A. *
8 L.R.A.
2 F.L.A. *
8 L.R.A.
240 VA Pilot Duty
(Motor Starter Coil)
9-10-11-20
Modulator
240 VA Pilot Duty
16-17-18-19
Fuel/Ignition
240 VA Pilot Duty
3
Alarm
125 VA Pilot Duty
* F.L.A. = full load amps; L.R.A = locked rotor amps
Maximum connected load must not exceed 2000VA.