ELECTRICAL RATINGS
VA ratings (not specified as pilot duty) permit the connection of transformers and similar devices whose
inrush current is approximately the same as their running current.
VA pilot duty ratings permit the connection of relays, solenoid valves, lamps, etc. whose total operating
load does not exceed the published rating and whose total inrush does not exceed 10 times the rating.
Running and locked rotor ratings are intended for motors. VA and VA pilot duty loads may be added to a
motor load provided the total load does not exceed the published rating.
OPERATIONAL TIMINGS
The BurnerPRO is pre-programmed from the factory with a set of operational timings necessary for the
safe operation of the burner system. However, operational timings can be modified via the Modbus port
using the 60-3000 ModBus Comms cable and BP-CON configuration software. The operational timings
are governed by regional and local codes. It is important that the appropriate operational timing is selected
for the burner application.
DIMENSIONS: FIG. 1
In Inches or [mm]